(4)Set the contents of the schedule
When one of the [Edit] buttons in the Contents of Schedule box is
clicked, a screen to set a schedule operation will appear. Use this
screen to set when to run an operation and set the type of schedule
operation (ON/OFF, operation mode, temperature setting, fan
direction, fan speed, prohibit remote controller operation) and then
press the [OK] button.
It is possible to schedule operation by specifying the settings for
selected items (e.g., operation mode only or preset temperature only).
Note: When [Optimized start] is selected, the unit starts 5 - 60 minutes
before the scheduled time based on the operation data history in
order to reach the scheduled temperature at the scheduled time.
(When the unit starts the first time after power reset, the
operation starts 30 minutes before the scheduled time.) When
using this function, also set the operation mode and setting
temperature. If "Prohibit Remote Controller" is set at the same time, remote controller is prohibited at its
setting time.
If the room temperature is measured by the air-conditioner's suction temperature sensor, the temperature
may not be correct when the air-conditioner is inactive and the air is not fresh. When the temperature is not
measured correctly, switch the sensor to external temperature sensor (PAC-SE40TSA) or remote control
sensor.
Note: Only air conditioner units can set [Optimized start].
Note: The CITY MULTI model supports a temperature setting range of 12-28°C / 53-83°F when in Heat mode.
(When S series (PUMY) is used, set the temperature at 17°C-28°C / 63-83°F in heat mode.)
Note: When setting a schedule for all groups or for a block, it is possible to set all operation modes such as Auto
mode etc, but if some targeted air conditioner units do not have such a function, then those units will not run in
the specified mode. When setting the schedule, consider what functions are supported by the air conditioner
units.
Note: When setting a schedule for all groups or for a block, it is possible to set prohibit remote controller items
individually. When allowing remote controller operation under K control, however, all items must be set
enable.
Note: When setting a schedule for ventilator units, the temperature setting and fan direction setting are not
displayed. Moreover, the prohibit remote controller operation is simply [ON/OFF].
Note: Only the ON/OFF operation is possible on the general equipment.
(5)Copy a schedule to another day of the week or to another
group
When copying a schedule between each day of the week, click [Copy
(Day of the week)] button. The color of the button turns to green
(which means the button is selected). Select the desired day, and click
[Paste] button.
When copying the entire week's schedule between groups, click
[Copy (Group)] button. Select the desired group, and click [Paste]
button.
Note: Copied schedule cannot be pasted to different type of
equipment. For example, schedule copied on the air conditioner
cannot be pasted to the ventilator equipment.
Note: The operation mode that can be pasted and the temperature
setting range vary depending on the unit type.
(6)Save the contents of schedule
After you have finished setting the contents of the schedule, save the
schedule setting by clicking the [Save Settings] button.
If the contents of the schedule setting have changed since the
previous save, you can click the [Undo] button to restore the setting
contents back to the saved settings.
32
OK Button
Copy (Day of the week) / Paste
Copy (Group) / Paste
Save Settings button