Current Cut - Mitsubishi SCM40ZS-S Technical Manual

Inverter multi-split system residential air-conditioners
Table of Contents

Advertisement

Error code
E42
Remote control:
1. Applicable model
All models
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
• The valves closed
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
LED
Green
Red
Keeps flashing
Stays OFF
Indoor
1-time flash
Outdoor
5. Troubleshooting
Diagnosis
Is the
Power source
voltage OK?
YES
Are the
service valves
opened?
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
coil wire resistance (1) of
compressor motor
OK?
Note (1) 1.703 or more at 20°C
YES
To next page.
265
-
Content

Current cut (1/2)

NO
NO
NO
NO
-
'16 • SCM-T-199
Countermeasure
Check power source.
Open the valves.
Check refrigerant amount
and refregerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compresser is
discharged from the
compressor.
Replace compressor.