Timer Operation - Mitsubishi SCM40ZS-S Technical Manual

Inverter multi-split system residential air-conditioners
Table of Contents

Advertisement

3)
Flap
Louver
4)
Flap
Louver
5)
Operation mode
Cooling
Heating
(b)
During DRY operation (including auto DRY operation)
Flap
Louver

(10) Timer operation

(a) Comfort start-up (ON timer operation)
(10) Timer operation
The unit starts the operation 5 to 60 minutes earlier so that the room can approach optimum temperature at ON timer.
(a) Comfort start-up (ON timer operation)
(b) Sleep timer operation
The unit starts the operation 5 to 60 minutes earlier so that the room can approach optimum temperature at ON timer.
(b) Sleep timer operation
(c) OFF timer operation
The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period.
(c) OFF timer operation
(d) Weekly timer operation
The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period.
Up to 4 programs with timer operation (ON timer / OFF timer) are available for each day of the week.
(d) Weekly timer operation
(11) Night setback operation
Up to 4 programs with timer operation (ON timer / OFF timer) are available for each day of the week.
(12) Air flow range setting
When the night setback operation is set, the heating operation starts with the setting temperature at 10 ℃ .
Take the air-conditioner location into account and adjust the left/right air flow range to maximize air-conditioning.
(12) Air flow range setting
(a) Setting
Take the air-conditioner location into account and adjust the left/right air flow range to maximize air-conditioning.
(i) If the air-conditioning unit is running, press the ON/OFF button to stop.
(a) Setting
(i) If the air-conditioning unit is running, press the ON/OFF button to stop.
(ii) Press the AIR FLOW U/D (UP/DOWN) button and the AIR FLOW L/R
(LEFT/RIGHT) button together for 5 seconds or more.
(ii) Press the AIR FLOW U/D (UP/DOWN) button and the AIR FLOW L/R
(LEFT/RIGHT) button together for 5 seconds or more.
(iii) Setting the air-conditioning installation location.
(iii) Setting the air-conditioning installation location.
(Center installation)
(Center installation)
Cooling
Up/down swing
Center (Fixed)
Cooling
Horizontal blowing (Fixed)
< =
Room temp. – Setting temp. 2°C
The control in 4) continues.
Setting temp. – Room temp. 2°C
< =
The control in 4) continues.
Horizontal blowing (Fixed)
Wide (Fixed)
L/R
L/R
L/R
L/R
(Right end installation)
(Left end installation)
(Right end installation)
(Left end installation)
-
4
Heating
Heating
Slant forwardl blowing (Fixed)
Wide (Fixed)
Air flow direction contorol
2°C < Room temp. – Setting temp. 5°C
Control returns to the control in 2).
2°C < Setting temp. – Room temp. 5°C
Control returns to the control in 2).
155
-
'16 • SCM-T-199
room
< =
Room temp. – Setting temp. > 5°C
Control returns to the control in 1).
< =
Setting temp. – Room temp. > 5°C
Control returns to the control in 1).
'09•SRK-DB-087D
'09•SRK-DB-087D