Inverter wall mounted type residential air-conditioner

Advertisement

Manual No.'12•SRK-T-130
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
INVERTER WALL MOUNTED TYPE
RESIDENTIAL AIR-CONDITIONER
(Split system, air to air heat pump type)
SRK92ZL-S

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi SRC92ZL-S

  • Page 1 Manual No.'12•SRK-T-130 RESIDENTIAL AIR-CONDITIONING TECHNICAL MANUAL & PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER (Split system, air to air heat pump type) SRK92ZL-S...
  • Page 2 TECHNICAL MANUAL...
  • Page 3: Table Of Contents

    '10 • SRK-T-105 '12 • SRK-T-130 CONTENTS 1. SPECIFICATION ..................2. EXTERIOR DIMENSIONS ................. (1) Indoor unit ..................(2) Outdoor unit ..................(3) Remote control ..................3. ELECTRICAL WIRING ................(1) Indoor unit ..................(2) Outdoor unit ..................4. NOISE LEVEL ....................
  • Page 4 '10 • SRK-T-105 '12 • SRK-T-130 (8) Phenomenon observed after shortcircuit, wire breakage on sensor ..58 ........... 59 (9) Checking the indoor electrical equipment (10) How to make sure of wireless remote control ........60 (11) Outdoor unit inspection points .............. 61 11.
  • Page 5: Specification

    1. SPECIFICATION Adapted to RoHS directive SRK92ZL-S Model Item Indoor unit SRK92ZL-S Outdoor unit SRC92ZL-S 1 Phase, 220 ~ 240V, 50Hz Power source Nominal cooling capacity (range) 9.2 ( 2.4 (Min.) - 10.0 (Max.)) Nominal heating capacity (range) 10.0 ( 2.2 (Min.) - 11.2 (Max.)) 2.54 ( 0.47 ~...
  • Page 6: Exterior Dimensions

    '12 • SRK-T-130 2. EXTERIOR DIMENSIONS (1) Indoor unit Model SRK92ZL-S RKW000Z402...
  • Page 7: Outdoor Unit

    '12 • SRK-T-130 (2) Outdoor unit Model SRC92ZL-S RCR000Z006...
  • Page 8: Remote Control

    '12 • SRK-T-130 (3) Remote control (a) Wireless remote control Unit: mm 17.3...
  • Page 9 '12 • SRK-T-130 (b) Wired remote control (option parts) Interface kit (SC-BIKN-E) is required to use the wired remote control. Wiring outlet Cut off the upper thin part of remote control lower case with a nipper or knife, and grind burrs with a file etc. Exposed mounting In case of pulling out In case of pulling out...
  • Page 10: Electrical Wiring

    '12 • SRK-T-130 3. ELECTRICAL WIRING (1) Indoor unit Model SRK92ZL-S RWA000Z402...
  • Page 11: Outdoor Unit

    '12 • SRK-T-130 (2) Outdoor unit Model SRC92ZL-S t゜ t゜ t゜ RWC000Z260...
  • Page 12: Noise Level

    Mike position as below ● 0.8m Unit Mike position (Center & Low points) (Outdoor Unit) Mike position: at highest noise level in position as mentioned below Model SRC92ZL-S ● Distance from front side 1m Noise Cooling 53 dB(A) Level Heating 54 dB(A) ×...
  • Page 13 Mike position as below ● 0.8m Unit Mike position (Center & Low points) (Outdoor Unit) Model SRC92ZL-S Mike position: at highest noise level in position as mentioned below ● Distance from front side 1m Cooling 58 dB(A) Noise Level Heating 60 dB(A) ×...
  • Page 14 Mike position as below ● 0.8m Unit Mike position (Center & Low points) (Outdoor Unit) Mike position: at highest noise level in position as mentioned below Model SRC92ZL-S ● Distance from front side 1m Noise Cooling 52 dB(A) Level Heating 60 dB(A) ×...
  • Page 15 '12 • SRK-T-130 Condition ISO-T1,JIS C9612 (4) Max value in Lo MODE Mike position as below ● (Indoor Unit) Model SRK92ZL-S 0.8m Cooling 41 dB(A) Unit Noise Mike position (Center & Low points) Level Heating 42 dB(A) × ..Cooling Heating Mike position: at highest noise level in position as mentioned belo ●...
  • Page 16 Mike position as below ● 0.8m Unit Mike position (Center & Low points) (Outdoor Unit) Mike position: at highest noise level in position as mentioned below Model SRC92ZL-S ● Distance from front side 1m Noise Cooling 42 dB(A) Level Heating 51 dB(A) ×...
  • Page 17: Piping System

    '12 • SRK-T-130 5. PIPING SYSTEM Model SRK92ZL-S Model SRK92ZL-S Cooling cycle Heating cycle Indoor unit Outdoor unit Outdoor air Flare temp. sensor connection Service valve (TH3) (Gas) Gas pipie Discharge pipe Check joint Heat temp. sensor Room temp. exchanger sensor (TH4) sensor...
  • Page 18: Range Of Usage & Limitation

    '12 • SRK-T-130 6. RANGE OF USAGE & LIMITATION 6. RANGE OF USAGE & LIMITATIONS Model SRK25ZJP-S1, 35ZJP-S1 SRK50ZJP-S1 SRK92ZL-S Item Cooling operation : Approximately 18 to 32℃ D.B. Indoor return air temperature Heating operation : Approximately 15 to 30℃ D.B. (Upper, lower limits) (Refer to the selection chart) Cooling operation : Approximately -15 to 46℃...
  • Page 19 '09•SRK-DB-087D '12 • SRK-T-130 (2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping Piping length [m] Cooling 0.99 0.975 0.965 0.95 0.935 Heating (3) Correction relative to frosting on outdoor heat exchanger during heating Air inlet temperature of 5 or more outdoor unit in °C WB...
  • Page 20: Capacity Table

    '12 • SRK-T-130 7. CAPACITY TABLE SRK92ZL-S Model Cool Mode (kW) Heat Mode(HC) (kW) Indoor air temp Indoor air temp Outdoor Air flow 21℃DB 23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB Outdoor air temp. Air flow air temp. 16℃DB 18℃DB 20℃DB 22℃DB 24℃DB 14℃WB 16℃WB 18℃WB...
  • Page 21 '12 • SRK-T-130...
  • Page 22 '12 • SRK-T-130...
  • Page 23 '12 • SRK-T-130...
  • Page 24 '12 • SRK-T-130...
  • Page 25 '12 • SRK-T-130...
  • Page 26 '12 • SRK-T-130...
  • Page 27 '12 • SRK-T-130...
  • Page 28 '12 • SRK-T-130...
  • Page 29 '12 • SRK-T-130...
  • Page 30 '12 • SRK-T-130...
  • Page 31 '12 • SRK-T-130...
  • Page 32: Outline Of Operation Control By Microcomputer

    '12 • SRK-T-130 9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Operation control function by remote control Operation section OPERATION MODE select button FAN SPEED button Each time the button pressed, the Each time the button is pressed, the display is switched over in turn. display is switched over in turn.
  • Page 33: Unit On/Off Button

    '09•SRK-DB-087D '12 • SRK-T-130 (2) Unit ON/OFF button (a) Operation (b) Details of operation Function Indoor temperature Fan speed Flap/Louver Timer Switch setting operation mode Cooling Thermal dry Unit ON/OFF button Heating (3) Auto restart function Jumper wire (J170) (ii) (J170) Jumper wire (J171) (4) Custom cord switching procedure...
  • Page 34: Selection Of The Annual Cooling Function

    '12 • SRK-T-130 (5) Selection of the annual cooling function (a) The annual cooling function can be enabled or disabled by means of the jumper wire (J172) on the indoor unit PCB and the dip switch (SW2-4) on the interface kit (option) PCB. Interface kit Jumper wire (SC-BIKN-E)
  • Page 35: Timer Operation

    display Center installation Left Approx. 50° Left Approx. 20° Center Right Approx. 20° Right Approx. 50° '12 • SRK-T-130 (c) Swing (ii) In HEAT operation In COOL, DRY, FAN operation Approx. 5° Approx. 35° Approx. 60° Approx. 80° (d) Memory flap (Flap or Louver stopped) (e) When not operating ( f ) Multi-directional Air Flow (up/down air scroll and left/right air scroll) Activating both up/down air swing and left/right air swing at the same time results in a multi-directional air flow.
  • Page 36: Outline Of Heating Operation

    (c) OFF timer operation '12 • SRK-T-130 (8) Outline of heating operation (a) Operation of major functional components in heating mode Heating Thermostat ON Thermostat OFF Failure Compressor ON(HOT KEEP) Indoor fan motor Outdoor fan motor (few minutes ON) 4-way valve (3 minutes ON) (b) Details of control at each operation mode (pattern) Fuzzy operation...
  • Page 37: Outline Of Cooling Operation

    '12 • SRK-T-130 1) 2) 3) − − (ii) 16 minutes and 50 seconds. ¡Defrast operation Heating operation '09•SRK-DB-087D Max. 16 minutes and 50 seconds 2~7 minutes '09•SRK-DB-087D Hot keep operation Depends on an operation condition, the time can be longer than 7 minutes. (9) Outline of cooling operation (9) Outline of cooling operation (a) Operation of major functional components in Cooling mode...
  • Page 38: Protective Control Function

    Dehumidifying Indoor air temperature (˚C) 18.0 Heating '12 • SRK-T-130 Outdoor air temperature (˚C)   When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on (ii) the difference between the setting temperature and the indoor air temperature. (iii) When the operation mode has been judged following the change of setting temperature with the remote control, the hourly judgment of operation mode is cancelled.
  • Page 39 '12 • SRK-T-130 When this control has continued for more than 0 minutes continuously, the following wind direction control is per- formed. a) When the vertical wind direction is set at other than the vertical swing, the flaps change to the horizontal position. b) When the horizontal wind direction is set at other than the horizontal swing, the louver changes to the vertical po- sition.
  • Page 40 reduced to 0 rps. (iii) Reset conditions: '12 • SRK-T-130 (d) Cooling high pressure control Purpose: (ii) Detector: (iii) Detail of operation: (Example) Fuzzy After lapse of 30 sec. or over 8rps After lapse of 30 sec. or over 8rps lower limit After lapse of 30 sec.
  • Page 41 '12 • SRK-T-130 Heating high pressure control Purpose: (ii) Detector: Detail of operation: (iii) (Example) Fuzzy After lapse of 20 sec. or over 4rps 8rps After lapse of 20 sec. or over 4rps 8rps lower limit After lapse of 20 sec. or over speed 20 rps 0rps Indoor heat exchanger temperature(°C)
  • Page 42 Normal operation '12 • SRK-T-130 Outdoor air temperature (°C) Reset conditions: Heating low outdoor temperature protective control  Operating conditions:   Detail of operation:   (ii) Lower limit 28 rps Lower limit 24 rps '09•SRK-DB-087D Normal operation Outdoor air temperature (°C) When either of the following condition is satisfied. Reset conditions: Reset conditions: (iii)
  • Page 43 Detail of operation: (ii) '12 • SRK-T-130 (k) Current cut Purpose: (ii) Detail of operation: Outdoor unit failure item (i), (ii) is satisfied. Once the unit is stopped by this function, ti is not (ii) '09•SRK-DB-087D (m) Indoor fan motor protection Serial signal transmission error protection Purpose: (ii)
  • Page 44 '12 • SRK-T-130 Reset conditions: (ii) Heating Operating conditions: Detail of operation: Reset conditions: Refrigeration cycle system protection Starting conditions When 5 minutes have elapsed after the compressor ON or the completion of the defrost control Other than the defrost control When, after meeting the conditions of 1) and 2) above, the compressor speed, indoor air temperature (Th1) and indoor heat exchanger temperature (Th2) have met the conditions in the following table for 5 minutes: Indoor air temperature (Th1)/...
  • Page 45: Maintenance Data

    '09•SRK-DB-087D '12 • SRK-T-130 Reference Reference 10. MAINTENANCE DATA 2 TROUBLESHOOTING PROCEDURES FOR ELECTRICAL EQUIPMENT (1) Cautions (2) Items to check before troubleshooting (3) Troubleshooting procedure (If the air conditioner does not run at all) Important...
  • Page 46: Troubleshooting Procedure (If The Air Conditioner Runs)

    '09•SRK-DB-087D '12 • SRK-T-130 (4) Troubleshooting procedure (If the air conditioner runs) 46 ~ 52. 46 ~ 52.
  • Page 47: Self-Diagnosis Table

    '09•SRK-DB-087D '12 • SRK-T-130 (5) Self-diagnosis table Wired Indoor unit display panel Outdoor remote Description Cause Display (flashing) condition control PCB control TIMER of trouble display light light Red LED • Broken heat exchanger sensor When a heat exchanger sensor 1 wire disconnection is detected while 1 time operation is stopped.
  • Page 48: Service Mode (Trouble Mode Access Function)

    '09•SRK-DB-087D '12 • SRK-T-130 (6) Service mode (Trouble mode access function) (a) Explanation of terms Explanation Term The service mode is the mode where service data are displayed by flashing of the display lights Service mode when the operations in item (b) below are performed with the indoor control. These are the contents of error displays and protective stops which occurred in the past in the air conditioner system.
  • Page 49 '12 • SRK-T-130 (i) Self-diagnosis data Remote control setting Contents of output data Indicates the number of Remote control setting occasions previous to the present Temperature setting the error display data are from. 21ºC 1 time previous (previous time) 2 times previous 22ºC 23ºC 3 times previous...
  • Page 50 '12 • SRK-T-130 (Example) Remote control setting Operation Displayed data Temperature Fan speed switching switching setting 21ºC Displays the reason for the stop (error code) the previous time an error was displayed. Displays the reason for the stop (error code) 2 times previous when an error was displayed. 22ºC Displays the reason for the stop (error code) 3 times previous when an error was displayed.
  • Page 51 '12 • SRK-T-130 (c) Error code, stop code table Number of flashes when in service mode Stop coad Error Auto TIMER Error content Cause Occurrence conditions display recovery light light Error coad (10's digit) (1's digit) Normal Can not receive signals for 35 Power supply is faulty.
  • Page 52 '12 • SRK-T-130 (d) Remote control information tables (ii) Display pattern when Display pattern when Fan speed in service mode in service mode Operation switching switching when when there is an there is an RUN light TIMER light abnormal stop abnormal stop (Operation switching) (Fan speed switching)
  • Page 53 '09•SRK-DB-087D '12 • SRK-T-130 (e) Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat exchanger sensor table Units: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) Sensor value displayed when the error code is normal Sensor name -64ºC...
  • Page 54 '12 • SRK-T-130 Discharge pipe sensor table Units: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) Sensor value displayed when the error code is normal -64ºC 0.1 sec. If the temperature is < 0, the buzzer sounds. If the temperature is≧0, the buzzer does not sound.
  • Page 55 '12 • SRK-T-130 Service data record form...
  • Page 56: Inspection Procedures Corresponding To Detail Of Trouble

    '09•SRK-DB-087D '12 • SRK-T-130 (7) Inspection procedures corresponding to detail of trouble Sensor error Broken sensor wire, connector poor connection Sensor temperature characteristics (Room Discharge pipe sensor temperature characteristics temp., indoor heat exchanger temp., out- door heat exchanger temp., outdoor air temp.) - 10 Temperature (˚C)
  • Page 57: Current Cut

    '12 • SRK-T-130 Current cut Compressor lock, Compressor wiring short circuit, Compressor output is open phase, Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty. *   * 0.510Ω or more at 20ºC Current safe stop Overload operation, compressor lock, overcharge...
  • Page 58 '09•SRK-DB-087D '12 • SRK-T-130 Over heat of compressor Gas shortage, defective discharge pipe sensor Error of signal transmission Wiring error including power cable, defective indoor/ outdoor PCB ② ③ ② ③ ① ②...
  • Page 59 '09•SRK-DB-087D '12 • SRK-T-130 Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor PCB ◆       Notes (1) Check coil resistance, see page 55. . Outdoor fan motor error Defective fan motor, connector poor connection, defective outdoor PCB the fan motor and outdoor...
  • Page 60 '12 • SRK-T-130 Rotor lock Defective compressor, defective outdoor PCB See page 55. (8) Phenomenon observed after shortcircuit, wire breakage on sensor (8) Phenomenon observed after shortcircuit, wire breakage on sensor (a) Indoor unit (a) Indoor unit Phenomenon Operation Sensor Phenomenon Operation mode...
  • Page 61 Shortcircuit Disconnected wire Cooling Heat exchanger sensor Defrosting is performed for 10 minutes at approx. 35 minutes. Heating Cooling Ourdoor air '12 • SRK-T-130 temperature sensor Defrosting is performed for 10 minutes at approx. 35 minutes. Heating Discharge pipe All modes sensor (9) Checking the indoor electrical equipment (a) Indoor PCB check procedure...
  • Page 62 '12 • SRK-T-130 (C) Power transistor inspection procedure [Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)] (1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.) If no problems are found, check the output of the power transistor.
  • Page 63 '09•SRK-DB-087D '12 • SRK-T-130 (11) Outdoor unit inspection points Model SRC92ZL-S 20ZJX-S, 25ZJX-S, 35ZJX-S t゜ t゜ t゜...
  • Page 64 '12 • SRK-T-130 (a) Inspection of electronic expansion valve (ii) white (iii) (iv) • Inspection of electronic expansion valve as a separate unit Measuring point Resistance when normal (b) Outdoor unit fan motor check procedure    CNFAN1 or CNFAN2    ②...
  • Page 65: Option Parts

    '12 • SRK-T-130 11. OPTION PARTS Installation manual for wired remote controller PJA012D730 Connect the remote control cord (1) Wired remote control (RC-E5) terminal block. Connect the terminal of remote c Read together with indoor unit's installation manual. with the terminal of indoor unit (X (X and Y are no polarity) WARNING Wiring route is as shown in the r...
  • Page 66 '12 • SRK-T-130 mote controller Connect the remote control cord to the Sheath Sheath The range of temperature setting Upper Upper terminal block. When shipped, the range of set tempera Connect the terminal of remote control (X,Y) Upper case Upper case Board Board Heating : 16 ~ 30°C (55 ~ 86°F)
  • Page 67 '12 • SRK-T-130 PJA0 12D7 30 Sheath Sheath The range of temperature setting Upper When shipped, the range of set temperature differs depending on the operation mode as below. Upper case Upper case Board Heating : 16 ~ 30°C (55 ~ 86°F) Except heating (cooling, fan, dry, automatic) : 18 ~ 30°C (62 ~ 86°F) Upper limit and lower limit of set temperature can be changed with remote control.
  • Page 68 '12 • SRK-T-130 The functional setting The initial function setting for typical using is performed automatically by the indoor unit connected, when remote control and indoor unit are connected. As long as they are used in a typical manner, there wiil be no need to change the initial settings. If you would like to change the initial setting marked “...
  • Page 69 '12 • SRK-T-130 Note 1: The initial setting marked “ ” is decided by connected indoor and outdoor unit, and is automatically defined as following table. Function No. Item Default Model "Auto-RUN" mode selectable indoor unit. Remote control function02 Indoor unit without "Auto-RUN" mode Indoor unit with two or three step of air flow setting Remote control function06...
  • Page 70 '12 • SRK-T-130 PJA 01 2D7 30 is automatically defined as following table. Operation message How to set function able indoor unit. Function description: Function No. Stop air-conditioner and press (SET) (MODE) setting description: -RUN" mode buttons at the same time for over three seconds, and the ree step of air flow setting "FUNCTION SET "...
  • Page 71: Safety Precautions

    '12 • SRK-T-130 (2) Interface kit (SC-BIKN-E) RKZ012A088B Accessories included in package Safety precautions Before use, please read these Safety Precautions thoroughly before installation. Be sure to check all the accessories included in package. ●All the cautionary items mentioned below are important safety related items to be taken into consideration, so be sure to observe them at all times.
  • Page 72 '12 • SRK-T-130 Installation of the interface ・Install the interface within the range of the connection cable length (approximately 1.3m) from the indoor unit. Wiring inlet ・Be sure not to extend the connection cable on site. If the connection cable is extended, malfunction may occur. ・Fix the interface on the wall, pillar or the like.
  • Page 73 '12 • SRK-T-130 Functions of CNT connector It is available to operate the air conditioning unit and to monitor the operation status with the external control unit (remote display) by sending the input/output signal through CNT connector on the indoor control PCB. 0.75mm Note (1) 0.3mm ×2m...
  • Page 74 '12 • SRK-T-130 Connection of wired remote control Regarding the connection of wired remote control, refer to the instruction manual of wired remote control. ①Switch ON the DIP switch SW2-2 (Factory setting : ON) on the interface PCB. DIP suitch Caution:Wireless remote control attached to the indoor unit can be used in parallel, after connecting the wired remote control.
  • Page 75 '12 • SRK-T-130 (3) Super link E board (SC-ADNA-E) SL2NA-E, and SL3N-AE/BE to control...
  • Page 76 '12 • SRK-T-130...
  • Page 77: Parts List

    '12 • SRK-T-130 PARTS LIST INDOOR UNIT SRK92ZL-S OUTDOOR UNIT SRC92ZL-S...
  • Page 78 '12 • SRK-T-130 CRAE0240...
  • Page 79 '12 • SRK-T-130 SRK92ZL-S END ITEM NO. : RWA002F070B Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1 6 RKW102A400 PANEL ASSY,FRONT 1 RKW122A400 PANEL,FRONT 2 RKW435A401 PANEL ASSY,AIR IN 3 RKW437A400 FILTER,AIR W458.5×H345.3(t2) 5 RKW133A401 PLATE,ORNAMENT 6 RKW011G400 LABEL,WIRING 7 31 RKW435A202G GRILLE ASSY,AIR OUT 7 RKW435A203B GRILLE,AIR OUTLET...
  • Page 80 '12 • SRK-T-130 SRK92ZL-S END ITEM NO. : RWA002F070B Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 42 43 RKW132A403 LID ASSY(TERMINAL) 43 RSA011H027 LABEL,NOTICE 44 RKW129A405 COVER,PIPE 45 RKW129A213 HOLDER,FILTER ×...
  • Page 81 '12 • SRK-T-130 MEMO...
  • Page 82 '12 • SRK-T-130 CRAE0258...
  • Page 83 '12 • SRK-T-130 SRK92ZL-S END ITEM NO. : RWA002F070B Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1 12 RMA301A003B HEAT EXCH ASSY(AIR) 2 RMA315D004A HEADER ASSY 3 RKW129A410 BRACKET ASSY(L) 4 7 RMA315A004 DISTRIBUTOR ASSY 4 RSA315A006 DISTRIBUTOR 5 RSA315D019 HEADER...
  • Page 84 '12 • SRK-T-130 CRBE0347...
  • Page 85 '12 • SRK-T-130 SRC92ZL-S END ITEM NO. : RWC003F089 Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1 RCR111A102 BASE ASSY 2・3 PCA122A062 PANEL ASSY,FRONT 3 SSA944B031A HANDLE 4・5 RCR122A101 PANEL ASSY,SERVICE 5 SSA944B031A HANDLE 6 RCR124A102 PANEL ASSY,TOP 7・8 RCR125A101...
  • Page 86 '12 • SRK-T-130 CRBE0348...
  • Page 87 '12 • SRK-T-130 SRC92ZL-S END ITEM NO. : RWC003F089 Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1~6 RCR301A102 HEAT EXCH ASSY(AIR) 2 RCR315D102 HEADER ASSY,GAS ▼ 3~6 RCR315A101 DISTRIBUTOR ASSY 3 RSA315A004A DISTRIBUTOR ▼ 4 RCR315B101 CAPILLARY 2.6×...
  • Page 88 '12 • SRK-T-130 CRBE0349...
  • Page 89 '12 • SRK-T-130 SRC92ZL-S END ITEM NO. : RWC003F089 Recommendable Purchased Q'ty Part No. Part Name RE.Q Note 1000 1 RCR116A115 BASE,MOTOR 2 SSA431B228 FAN,PROPELLER 3 SSA512T076S MOTOR,DC 4 SSA512T076R MOTOR,DC 5 SSA914H014A NUT,CAP 6 SSA915F002D WASHER(TH-INT) 7 SSA913C021A SCREW,TAP...