Error code
None
Remote control:
1. Applicable model
All models
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Defective remote control
• Malfunction by noise
• Faulty indoor power PCB
• Broken harness
• Faulty indoor control PCB
Note:
LED
Green
Red
Keeps flashing 3-time flash
Indoor
Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
loose connection of remote
control wire broken or
Disconnect remote
higher detected between X-Y
of indoor unit terminal
between
241
-
Content
Power source system error
(Power source to remote control)
Isn't there any
YES
control wires?
NO
Isn't remote
YES
short-circuited?
NO
control wires.
Is DC15V or
YES
block?
NO
Is DC180V
-
of CNW1
NO
(FDTC:CNW2)?
YES
-
'16 • SCM-T-199
Countermeasure
Correct.
Replace wires.
Replace remote control.
Defective indoor power
PCB → Replace.
Defective indoor control
PCB → Replace.