(4) High power operation

Pressing the HI POWER/ECONOMY button intensifies the operating power and initiates powerful cooling and heating operation
for 15 minutes continuously. The wireless remote control displays and the FAN SPEED display disappears.
(a) During the HIGH POWER operation, the room temperature is not controlled. When it causes an excessive cooling and heating,
press the HI POWER/ECONOMY button again to cancel the HIGH POWER operation.
(b) HIGH POWER operation is not available during DRY and the program timer operations.
(c) When HIGH POWER operation is set after ON timer operation, HIGH POWER operation will start from the set time.
(d) When the following operation are set, HIGH POWER operation will be canceled.
① When the HI POWER/ECONOMY button is pressed again.
② When the operation mode is changed.
③ When it has been 15 minutes since HIGH POWER operation has started.
(e) Not operable while the air-conditioner is OFF.
(5) Economy operation
Pressing the HI POWER/ECONOMY button initiate a soft operation with the power suppressed in order to avoid an excessive
cooling or heating. The unit operate 1.5℃ higher than the setting temperature during cooling or 2.5℃ lower than that during
heating. The wireless remote control displays ECONOMY mark and the FAN SPEED display disappears.
(a) It will go into ECONOMY operation at the next time the air-conditioner runs in the following cases.
① When the air-conditioner is stopped by ON/OFF button during ECONOMY operation.
② When the air-conditioner is stopped in SLEEP or OFF timer operation during ECONOMY operation.
③ When the operation is retrieved from CLEAN operation.
(b) When the following operation are set, ECONOMY operation will be canceled.
① When the HI POWER/ECONOMY button is pressed again.
② When the operation mode is changed DRY to FAN.
(c) Not operable while the air-conditioner is OFF.
(d) The setting temperature is adjusted according to the following table.
Mode
Item
Temperature
adjustment
(6) Air flow direction adjustment
Air flow direction can be adjusted with by AIR FLOW
(a) Flap
Each time when you press the AIR FLOW
(Flap stopped)
Angle of flap from horizontal
Wireless remote
control display
COOL , DRY
HEAT
Cooling
Heating
①+0.5
①-1.0
②+1.0
②-2.0
③+1.5
③-2.5
 
(UP/DOWN) button the mode changes as follows.
Approx. 15°
Approx. 25°
Approx. 25°
Approx. 35°
① at the start of operation.
② one hour after the start of operation.
③ two hours after the start of operation.
 
(UP/DOWN) button on the wireless remote control.
Approx. 35°
Approx. 45°
Approx. 50°
Approx. 59°
163
-
-
'16 • SCM-T-199
(Swing)
Approx. 59°
Approx. 65°