Device Functions Proline Promass 83 MODBUS RS485
Endress+Hauser
6.2
Group HANDLING TOTALIZER
→
TOTALIZER
D
TOTALIZER → HANDLING TOTALIZER → Handling totalizer functions
RESET ALL
3800
TOTALIZERS
MODBUS register:
2609
Data type:
Integer
Access:
read/write
FAILSAFE ALL
3801
TOTALIZERS
MODBUS register:
2607
Data type:
Integer
Access:
read/write
TOTALIZER 1
DAA
TOTALIZER 2
DAB
TOTALIZER 3
DAC
HANDLING TOTALIZER
DJA
Function description
Resets the totals and the overflows of all totalizers to zero.
Options:
0 = NO
1 = YES
Factory setting: NO
!
Note!
If the device has a status input and if it is appropriately configured, a reset for the
totalizer (1 to 3) can also be triggered by a pulse (see the ASSIGN STATUS INPUT
function (5000) on Page 103).
Use this function to define the common response of all totalizers (1 to 3) to error.
Options:
0 = STOP
The totalizer is paused until the fault is rectified.
1 = ACTUAL VALUE
The totalizer continues to count based on the current flow measuring value. The
fault is ignored.
2 = HOLD VALUE
The totalizer continues to count the flow that is based on the last valid flow value
(before the fault occurred).
Factory setting: STOP
6 Block TOTALIZER
→
Handling totalizer functions
57