Application; Technical Characteristics; Input Types - PR 5114 Manual

Programmable transmitter
Table of Contents

Advertisement

PROGRAMMABLE TRANSMITTER 5114
• Input for RTD, TC, mV, linear resistance, mA, and V
• 3-port 3.75 kVAC galvanic isolation
• Current and voltage output
• Universal voltage supply
• 1- and 2-channel versions
• Loop supply > 17.1 V in Ex zone 0

APPLICATION

Electronic temperature measurement with resistance sensor or thermocouple
sensor. • Ex barrier for temperature sensors, potentiometers, and current / voltage
signals • Ex power supply for 2-wire transmitters in zone 0, 1, 2, 20, 21, and
22. • Amplification of mV signals. • Conversion of linear resistance variation.
• Galvanic isolation of analogue signals. • Measurement of floating signals.
• Linearisation of non-linear Ohm, mV, mA, or voltage signals. • Separation of circuits
in PELV/SELV installations. • The transmitter is especially suitable for emitting the
output current signal, either as a standard current signal or as a loop signal.

TECHNICAL CHARACTERISTICS

The unit is based on a microprocessor core with an efficient program operation.
The basic calibration data and present set-up are stored in an EEPROM thereby
avoiding the loss or change of data at power off. The 2-channel version has a full
galvanic isolation between the channels. By way of jumpers on the PCB the input
in the standard version can be programmed either for a temperature or a current /
voltage input. This means that one channel can work as for instance a temperature
transmitter and the other can work as an isolation amplifier. Measurement range,
signal parameters, and output span are configured to the present task by way of a
PC and PR electronics A/S' communica tions interface Loop Link.

INPUT TYPES

Temperature input - jumpers in position 1:
Thermocouple input (TC) for standard thermocouples type B, E, J, K, L, N, R, S, T, U,
W3, W5, LR according to the norms IEC 584, DIN 43710, ASTM E988-90 and GOST
3044-84. The CJC can be selected in 3 different ways: internally in the terminal,
externally by way of a Pt100 / Ni100 sensor, or externally with a constant
temperature.
6
5114V10 7 -UK