How To Dismantle System 4000; When Front Led Lights Red / Display Shows Ao.er; Advanced Features; Application - PR PReasy 4116 Manual

4116v103-in
Table of Contents

Advertisement

Available languages

Available languages

hoW To disManTle sysTeM 4000

First, remember to demount the connectors with hazardous voltages.

When front led lights red / display shows ao.er

PR 4116 is designed as a SIL 2 device with a high safety level. Therefore, a
continuous measurement of the outgoing current is carried out on a 4...20
mA output signal. If the current is 0, an error mode switches on the red front
LED and disables the relays. This function is not a default option but must be
actively selected in the menu. The error mode can only be reset by switching
off and then switching on the supply voltage to the device.
38
Picture 1:
Detach the device from the DIN rail
by lifting the bottom lock.
Universal TransMiTTer
Preasy 4116
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• FM-approved for installation in Div. 2
• Output for current, voltage and 2 relays
• Universal AC or DC supply

advanced features

• Programmable via detachable display front (4501), process calibration, signal
and relay simulation, password protection, error diagnostics and selection of
help text in several languages.

application

• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analogue current /
voltage signal, i.e. from solenoids and butterfly valves or linear movements
with attached potentio meter.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 pairs of potential-free relay contacts and analogue
output.
• Galvanic separation of analogue signals and measurement of floating signals.
• The 4116 is designed according to strict safety requirements and is thus suit-
able for application in SIL 2 installations.
Technical characteristics
• When 4116 is used in combination with the 4501 display / programming front,
all operational parameters can be modified to suit any application. As the
4116 is designed with electronic hardware switches, it is not necessary to
open the device for setting of DIP switches.
• A green / red front LED indicates normal operation and malfunction. A yellow
LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 4-port 2.3 kVAC galvanic isolation.