Installation
To ensure full functionality of the ID Flag Sensor, follow the instructions provided in this section for
installation.
Installation Site
Do not install the ID Flag Sensor in the following locations.
• Locations exposed to ambient temperatures that are not between −10 and 55°C or where there are
radical temperature changes resulting in condensation
• Locations exposed to humidity that is not between 25% and 85%
• Locations subject to corrosive gas, flammable gas, dust, salt, or metal powder
• Locations that will expose the ID Flag Sensor to direct vibration or shock
• Locations exposed to direct sunlight
• Locations exposed to spray of water, oil, or chemicals
• Locations more than 2,000 m above sea level
Mounting in a Panel
The ID Flag Sensor can be used at an ambient temperature range of −10 to 55°C. Be sure to observe
the following precautions.
• Make sure that the Unit is provided with sufficient ventilation space.
• Do not install the Unit close to heaters, transformers, or large-capacity resistors that radiate excessive
heat.