Irig-B Connections; Irig-B Input Adapter - GE Multilin D400 Instruction Manual

Substation gateway
Hide thumbs Also See for Multilin D400:
Table of Contents

Advertisement

CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS
To connect fiber optic
links to the Fiber Optic
adapters

IRIG-B connections

IRIG-B input adapter

D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
Figure 35: D400 Plastic Optical Fiber Serial adapter
It is possible to saturate the receiver input if the cable used is too short. Inline attenuation
may be required.
See "Fiber optic serial adapter" on page 43 for configuration options.
Plug fiber optic cables into the corresponding TX and RX connectors.
The D400 uses a pair of IRIG-B adapter cards, the IRIG-B Input Adapter and the IRIG-B
Distribution Adapter, to accept an IRIG-B signal from a GPS receiver then distribute the
signal to connected IEDs.
See "IRIG-B input adapter" on page 44 and "IRIG-B distribution adapter" on page 47 for
more information.
The IRIG-B Input Adapter (GE Item No. 520-0211LF) plugs into a dedicated IRIG-B slot (slot
9) on the D400. The IRIG-B Input card accepts an IRIG-B signal in one of three input formats
through a corresponding connector type:
Modulated IRIG-B through a BNC connector
Pulse width coded IRIG-B (TTL) through a terminal block
Fiber Optic through a Receive (RX) 820-850 nm ST connector
Terminal blocks accept a range of 24 to 14 AWG [0.2 to 2.1 mm²] Recommended wire strip
length is 0.2" [5.0 mm]. Screws shall be torqued with tool setting of 4.2 in-lb [0.46 Nm]. A 3.0
to 3.5 mm flat screwdriver tip is recommended.
You can use the following glass optical fiber (GOF) cabling with the D400 Glass Optical
Fiber Serial adapter:
50/125 µm core/cladding multi-mode (gradient index) cable
62.5/125 µm core cladding multi-mode (gradient index) cable
100/140 µm core/cladding multi-mode (gradient index) cable
200 m core Hard-Clad Silica (HCS) multi-mode (step index) cable
You can use the following fiber optic terminations for D400 cabling:
ST Connectors
When calculating cable length, consider the following optical power levels:
Glass optical fiber receiver sensitivity is typically –25.4 dBm
GE INFORMATION
63