CHAPTER 13: SERVICING THE D400
To change the User
CompactFlash card

Replacing the power supply

D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
Figure 67: Replace the main CompactFlash card
Eject button
Connector P2
1.
Power down the D400.
2.
Using a Phillips Screwdriver, remove the screws from the CompactFlash slot cover
located on the front panel of the D400 main module.
3.
Press the Eject button to eject the CompactFlash card.
4.
Insert the new CompactFlash card into the slot.
5.
Replace the CompactFlash slot cover and secure it with the screws.
6.
Power up the D400.
Figure 68: Change the user CompactFlash card
The D400 may contain one or two power supplies (AC-DC and/or DC/DC) in the power
supply slots. The D400 may be supplied with an optional redundant power supply (in Slot 2)
to provide dual hot swappable power supplies. The power supply module is accessible and
easily replaced from the D400 front panel.