Reset file persistence data

Configure local HMI

148
Use this command to reset the data being stored by the File Based Persistence application
in the D400 mSQL database. This command permanently deletes data stored in the
Persistence Files of the D400.
After you have reset the data stored in the Persistence Files, you must restart the D400. It is
advised to restart the File Based Persistence application when the
user action.
You can configure the settings of the local KVM monitor output through the
menu. The Local HMI settings are described in Table 40.
Table 40: Local HMI setting descriptions
Setting
Current Settings
Desktop Mode
Monitor
DPMS
Screen Resolution
Monitor Type
GE INFORMATION
CHAPTER 12: USING THE D400 LOCAL CONFIGURATION UTILITY
Description
Use this command to view the existing Local HMI Settings.
Use this function to enable or disable "kiosk" mode. Kiosk mode
displays the local HMI in a full screen rather than within a Window.
Use this function to enter the horizontal and vertical refresh rates, in
Hertz.
Never exceed the maximum refresh rates of your monitor as
damage may occur. Refer to the manual that came with your
monitor for more information.
Use this function to enable or disable DPMS (Display Power
Management Signaling). These settings determine how much time
must pass without user interaction before your monitor is put into a
reduced power mode. A setting of "00" prevents the D400 from
triggering the power mode.
The following modes are available:
Stand-by: Monitor blanks but power supply remains on; screen
restores in approximately one second when reactivated by
keyboard or mouse input by user.
Suspend: Monitor power supply shuts off; screen restores in
approximately 2-3 seconds.
Turned off: Monitor is fully powered down except for an auxiliary
circuit to detect a wake-up signal; screen restores in
approximately 8-10 seconds
Note : Refer to the manual that came with your monitor for more
information on how it receives and responds to DPMS signals.
Use this function to select one of three output resolutions:
1280 x 1024
1024 x 786
800 x 600
Never exceed the maximum resolution of your monitor as damage
may occur. Refer to the manual that came with your monitor for
more information.
Select the type of monitor:
Standard
EL0 1379L
Fanuc IMpact
eGalax Touch
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
prompts for
d400cfg
Local HMI