Example System Configuration - GE Multilin D400 Instruction Manual

Substation gateway
Hide thumbs Also See for Multilin D400:
Table of Contents

Advertisement

CHAPTER 10: INTRODUCING THE D400 CONFIGURATION

Example System Configuration

Remote access
Local access to
via web-based HMI
command line via
RS232 port
PC clock is set to
No configuration
local time zone ( -8 )
necessary
If an event occurs at 13:00 UTC...
Event timestamp is
Event timestamp is
displayed as 05:00
displayed as 06:00
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
Figure _ shows an example system configuration.
Figure 58: Sample system configuration
D400
Even though the
in the local time zone of UTC -7, the
system clock is set to UTC time.
d400cfg System Clock: UTC time
d400cfg Time Zone: -7
D400
The
system database records the
event timestamp as 13:00
†This field is configured in minutes, so the value entered in the configuration tool would be
-420 and -300 respectively. However, hours are shown in the diagram above for clarity.
device is located
Local device with
D400
clock set to UTC -7
DNP Client Map File
Time Offset : -7
Local device reports
the event at 06:00
GE INFORMATION
Remote client with clock
set to UTC -5
DNP Server Application
Parameters Time Offset : -5
Remote client receives the
event timestamp as 08:00