D400 Substation Gateway
Appendix B: Installing and
Connecting DNP3 I/O Modules
Overall procedure to install and connect DNP3 I/O
modules
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
Installing and Connecting DNP3 I/O Modules
This Appendix describes how to install and connect DNP3 I/O modules, and connect to the
D400.
For more details on the DNP3 I/O module, refer to the 994-0085 Installation and
Maintenance Guide.
To install and connect DNP3 I/O modules:
1.
Configure the DNP3 I/O module from the D400 HMI.
See section "D400 connection to DNP3 I/O modules" on page 71 for the procedure to
configure the D400.
2.
Physically locate and mount DNP3 I/O module in a 19 inch rack or cabinet.
See section "Installing DNP3 I/O modules in a rack".
3.
Connect the DNP3 I/O module to site ground.
See section "Connecting to protective ground" on page 176.
4.
Interconnect the DNP3 I/O modules and connect power:
For low voltage DNP3 I/O, see section "Connecting DNP3 I/O modules (Low
Voltage)" on page 178.
For high voltage DNP3 I/O where connection is made to an external power supply,
see section "Connecting DNP3 I/O modules (High Voltage)" on page 180.
5.
Turn power on to the module, and test it to make sure it is functioning properly.
It is recommended that you complete the above procedure before connecting and testing
your field wiring.
GE INFORMATION
175