Power supply

Automatic record retrieval manager

156
The D400 provides a hard wired power supply failure alarm circuit as well as power supply
failure pseudo points through the system status manager. By default, the power supply
failure alarm is triggered whenever one or both supplies fail (single PSU alarm mode).
However, you can configure the D400 to only trigger an alarm when both supplies have
failed (redundant PSU alarm mode). The Power Supply settings are described in Table 48.
Table 48: Power supply setting descriptions
Setting
Configure Power Supply
Failure Alarm Mode
Table 49: Power supply operation - alternate alarm modes
Power Supply Unit Operation
Both supplies failed
Single supply failed
Both supplies operating
From the
menu, you can configure the Automated Record Retrieval Manager (ARRM)
ARRM
which retrieves and stores record files from devices connected to the D400. For example,
the SELBinary DCA application retrieves and archives the Event Log files from the SEL IEDs/
numerical relays.
The Automated Record Retrieval Manager settings are described in Table 50.
ARRM uses the Distributed Network Protocol (DNP) and the IEC 61850 protocol to
communicate with a variety of devices and uses the Trivial File Transfer Protocol (TFTP) or
MMS to transmit the files from the IED to the device over a local area network (LAN) or
serial connection.
Retrieved files are stored on the D400 file system in the folder /mnt/datalog/arrm/ with the
structure Company > Station > Device.
Table 50: Automated Record Retrieval Manager setting descriptions
Setting
Delete Records
GE INFORMATION
CHAPTER 12: USING THE D400 LOCAL CONFIGURATION UTILITY
Description
Use this function to display the power fail alarm mode that is
configured. You then have the option of switching to the alternate
alarm mode (see Table 49) for the Power Supply Unit (PSU).
Note : You must have FPGA version 2.0 or greater installed for this
feature to work. To check the FPGA version, enter dmesg -s 16392 |
grep -i FPGA at the D400 #>> command prompt and search for
FPGA in the output.
Alarm Mode
Redundant PSU
Alarm triggered
Alarm triggered
No alarm
Description
You can use the ARRM menu to delete the contents of these folder
structures, as well as temp and cache files, while leaving the
directory structure intact for future downloads.
You can also retrieve downloaded records from the D400 using any
FTP/SCP/SFTP client as needed or on a scheduled basis
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
Single PSU
Alarm triggered
No alarm
No alarm