Maintenance

Safety

General

The inverter is designed so that it does not require additional maintenance. However, there
are a few points to keep in mind during operation to ensure that the inverter functions op-
timally.
Opening Fronius
Procedure for opening the inverter for service or maintenance:
IG TL for service/
maintenance
1
2
3
4
5
6
7
8
9
10
11
WARNING! An electric shock can be fatal. Danger from grid voltage and DC volt-
age from solar modules.
-
The DC main switch is used only to switch off power to the power stage set.
When the DC main switch is turned off, the connection area is still energized.
-
Only licensed electricians should access the connection area.
-
All maintenance and service work should only be carried out when the power
stage set has been disconnected from the connection area.
-
Maintenance and service work on the inverter power stage set should only
be carried out by Fronius-trained personnel.
WARNING! An electric shock can be fatal. Danger from residual voltage from ca-
pacitors.
You must wait until the capacitors have discharged. Discharge takes 3 minutes.
CAUTION! An inadequate grounding conductor connection can cause serious in-
juries to persons and damage to (or loss of) property.
The housing screws provide an adequate grounding conductor connection for the
housing ground and should not, under any circumstances, be replaced by differ-
ent screws that do not provide a proper grounding conductor connection.
Disconnect the AC supply from the inverter.
Turn off the main DC switch.
Allow the capacitors to discharge (3 minutes).
Remove the 6 side screws.
Remove the power stage set from the wall bracket.
Protect the wall bracket from soiling and moisture.
Remove the 4 cover screws.
Carefully lift up the housing cover on the bottom of the power stage set.
Reach into the opening.
Disconnect the ribbon cable from the PC display board.
Remove the cover.
115