22 Start-up and control with I/O
Check the direction of the motor rotation.
• If the drive is in remote control (REM shown on
the left), switch to local control by pressing
.
LOC
REM
• To go to the Main menu, press
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
• Press keys
and press
• Increase the frequency reference from zero to
a small value with key
• Press
to start the motor.
• Check that the actual direction of the motor is
the same as indicated on the display (FWD
means forward and REV reverse).
• Press
to stop the motor.
To change the direction of the motor rotation:
• If parameter 9914 PHASE INVERSION is not
visible, first set parameter
VIEW to 3 (LONG VIEW).
• Invert the phases by changing the value of
parameter 9914 to the opposite, ie from 0 (NO)
to 1 (YES), or vice versa.
• Verify your work by applying input power and
repeating the check as described above. Set
parameter 9914 back to 2 (SHORT VIEW).
Check that the drive state is OK.
Basic Control Panel: Check that there are no
faults or alarms shown on the display. If you want
to check the LEDs on the front of the drive, switch
first to remote control (otherwise a fault is
generated) before removing the panel and
verifying that the red LED is not lit and the green
LED is lit but not blinking.
Assistant Control Panel: Check that there are no
faults or alarms shown on the display and that the
panel LED is green and does not blink.
DIRECTION OF THE MOTOR ROTATION
/
until you see "rEF"
.
.
1611
PARAMETER
FINAL CHECK
The drive is now ready for use.