Parameters
No.
Name/Value
USER S2
LOAD
USER S2
SAVE
9905 MOTOR NOM
VOLT
115...345 V
(200 V units)
200...600 V
(400 V E unit)
230...690 V
(400 V U units)
9906 MOTOR NOM
CURR
0.2...2.0 · I
2N
9907 MOTOR NOM
FREQ
10.0...500.0 Hz Frequency
9908 MOTOR NOM
SPEED
50...18000 rpm Speed
9909 MOTOR NOM
POWER
0.2...3.0 · P
kW Power
N
Actual values and parameters in the short view 33
Description
User 2 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 2 macro. Stores the current parameter settings
and the motor model.
Defines the nominal motor voltage. Must be equal to the
value on the motor rating plate. The drive cannot supply the
motor with a voltage greater than the input power voltage.
Output voltage
9905
WARNING! Never connect a motor to a drive which
is connected to power line with voltage level higher
than the rated motor voltage.
Voltage.
Note: The stress on the motor insulations is always
dependent on the drive supply voltage. This also applies to
the case where the motor voltage rating is lower than the
rating of the drive and the supply of the drive.
Defines the nominal motor current. Must be equal to the
value on the motor rating plate.
Current
Defines the nominal motor frequency, ie the frequency at
which the output voltage equals the motor nominal voltage:
Field weakening point = Nom. frequency · Supply voltage /
Motor nom. voltage
Defines the nominal motor speed. Must be equal to the
value on the motor rating plate.
Defines the nominal motor power. Must equal the value on
the motor rating plate.
Output frequency
9907
Def/FbEq
-2
-3
230 V
(200 V
units)
400 V
(400 V
E units)
460 V
(400 V
U units)
1 = 1 V
I
2N
1 = 0.1 A
E: 50.0 Hz
U: 60.0 Hz
1 = 0.1 Hz
Type
dependent
1 = 1 rpm
P
N
1 = 0.1
kW/hp