VM_MOTOR1_CURRENT_LIMIT
Units
%
Range of [MIN]
0.0
Range of [MAX]
0.0 to 1000.0
VM_MOTOR1_CURRENT_LIMIT[MAX] is dependent on the drive rating and motor set-up parameters.
VM_MOTOR1_CURRENT_LIMIT[MIN] = 0.0
Open-loop
VM_MOTOR1_CURRENT_LIMIT[MAX] = (I
Where:
I
MaxRef
duty), otherwise it is the lower of 0.7 x Pr 11.061 or 1.1 x Pr 11.060 (i.e. Normal Duty).
Where:
Definition
For example, with a motor of the same rating as the drive and a power factor of 0.85, the maximum current limit is
165.2%.
The rated active and rated magnetising currents are calculated from the power factor (Pr 05.010) and motor rated
current (Pr 05.007) as:
RFC-A
VM_MOTOR1_CURRENT_LIMIT[MAX] = (I
Where:
For VM_MOTOR2_CURRENT_LIMIT[MAX] use Pr 21.007 instead of Pr 05.007 and Pr 21.010 instead of Pr 05.010.
VM_MOTOR2_CURRENT_LIMIT
Units
%
Range of [MIN]
0.0
Range of [MAX]
0.0 to 1000.0
VM_MOTOR2_CURRENT_LIMIT[MAX] is dependent on the drive rating and motor set-up parameters.
VM_MOTOR2_CURRENT_LIMIT[MIN] = 0.0
Definition
Refer to VM_MOTOR1_CURRENT_LIMIT for more information. For VM_MOTOR2_CURRENT_LIMIT[MAX] use
Pr 21.007 instead of Pr 05.007 and Pr 21.010 instead of Pr 05.010.
78
Electrical
Getting
Basic
installation
started
parameters
Range applied to current limit parameters (motor 1)
-1
I
= I
x cos(sin
(I
Tlimit
MaxRef
Mrated
= Pr 05.007 sin φ
I
Mrated
= Pr 05.007 x cos φ
I
Trated
cos φ = Pr 05.010
is 0.7 x Pr 11.061 when the motor rated current set in Pr 05.007 is less than or equal to Pr 11.032 (i.e. Heavy
MOTOR1_CURRENT_LIMIT_MAX
Motor rated current is given by Pr 05.007
PF is motor rated power factor given by Pr 05.010
(MOTOR2_CURRENT_LIMIT_MAX is calculated from the motor map 2 parameters)
The Maximum current is (1.5 x Rated drive current) when the rated current set by Pr 05.007 (or Pr 21.007 if motor
map 2 is selected) is less than or equal to the Maximum Heavy Duty current rating specified in Pr 11.032, otherwise
it is (1.1 x Maximum motor rated current).
rated active current = power factor x motor rated current
rated magnetising current = √(1 - power factor
-1
I
= I
x cos(sin
(I
Tlimit
MaxRef
Mrated
I
= Pr 05.007 x cos φ
Mrated
1
ITrated = Pr 05.007 x sin φ
1
φ
= cos-1 (Pr 05.010) + φ
. φ
1
2
1
in the Parameter Reference Guide for more information regarding φ
I
is 0.9 x Pr 11.061 when the motor rated current set in Pr 05.007 is less than or equal to Pr 11.032 (i.e.
MaxRef
Heavy duty), otherwise it is the lower of 0.9 x Pr 11.061 or 1.1 x Pr 11.060 (i.e. Normal Duty).
Range applied to current limit parameters (motor 2)
Running
NV Media Card
Optimization
the motor
Operation
/ I
) x 100 %
Tlimit
Trated
/ I
))
MaxRef
Maximum current
------------------------------------------------------ -
Motor rated current
=
--------------------------------------------------------------------------------------------------------
PF
2
) x motor rated current
/ I
) x 100 %
Tlimit
Trated
/ I
))
MaxRef
is calculated during an autotune. See the variable minimum / maximum calculations
Onboard
Advanced
Diagnostics
PLC
parameters
2
2
(
)
+
PF
1
×
100%
.
2
Unidrive M400 Control User Guide