Emerson Unidrive M400 Series User Manual page 142

Variable speed ac drive for induction motors
Hide thumbs Also See for Unidrive M400 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Data Changing
Drive parameters are being changed
A user action or a file system write is active that is changing the drive parameters and the drive has been commanded to
enable, i.e. Drive Active (10.002) = 1.
The user actions that change drive parameters are loading defaults, changing drive mode, or transferring data from an NV
memory card to the drive. The file system actions that will cause this trip to be initiated if the drive is enabled during the
transfer are writing a parameter or macro file to the drive, or transferring a user program to the drive. It should be noted that
none of these actions can be started if the drive is active, and so the trip only occurs if the action is started and then the
drive is enabled.
97
Recommended actions:
Ensure the drive is not enabled when one of the following is being carried out:
DCCT Ref
DCCT Reference out of range for size 5 upwards only
Recommended actions:
110
Hardware fault - Contact the supplier of the drive
Derivative ID
Derivative file error
Derivative file error with sub-trips:
Sub-trip
246
Recommended actions:
Contact the supplier of the drive
142
Electrical
Getting
Basic
installation
started
parameters
Loading defaults
Transferring user program
Changing drive mode
Transferring data from NV Media Card
Reason
1
The derivative file is missing or is invalid
The derivative file does not match the
2
control board hardware
The derivative file has been changed for a
3
file with a different derivative number.
Running
NV Media Card
Optimization
the motor
Operation
Occurs when the drive powers-up. Load valid derivative file
matching the control board hardware.
Occurs when the drive powers-up. Load valid derivative file
matching the control board hardware.
Occurs when the drive powers-up or the file is
programmed. The file tasks will not run.
Onboard
Advanced
Diagnostics
PLC
parameters
Comments
Unidrive M400 Control User Guide
Issue Number: 1
UL
information

Hide quick links:

Advertisement

Table of Contents
loading