This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
22
Recommended actions:
Check enclosure / drive fans are still functioning correctly
Force the heatsink fans to run at maximum speed
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce the drive switching frequency
Reduce duty cycle
Increase acceleration / deceleration rates
Use S Ramp Enable (02.006)
Reduce motor load
Check the derating tables and confirm the drive is correctly sized for the application.
Use a drive with larger current / power rating
OI ac
Instantaneous output over current detected
The instantaneous drive output current has exceeded Pr 11.061.
This trip cannot be reset until 10 s after the trip was initiated.
Recommended actions/checks:
Increase acceleration/deceleration rate
If seen during auto-tune reduce the voltage boost
3
Check for short circuit on the output cabling
Check integrity of the motor insulation using an insulation tester
Is the motor cable length within limits for the frame size?
Reduce the values in the frequency loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
Reduce the values in the current loop gain parameters - (Pr 04.013, Pr 04.014)
OI Snubber
Snubber over-current detected
This trip indicates that an over-current condition has been detected in the rectifier snubbing circuit, The exact cause of the
trip can be identified by the sub-trip number.
Source
Power
system
92
Recommended actions:
Ensure the internal EMC filter is installed.
Ensure the motor cable length does not exceed the maximum for selected switching frequency.
Check for supply voltage imbalance.
Check for supply disturbance such as notching from a DC drive.
Check the motor and motor cable insulation with an insulation tester.
Fit an output line reactor or sinusoidal filter.
OI Brake
Braking IGBT over current detected: short circuit protection for the braking IGBT activated
The OI Brake trip indicates that over current has been detected in braking IGBT or braking IGBT protection has been
activated. This trip cannot be reset until 10 s after the trip was initiated.
Recommended actions:
4
Check brake resistor wiring
Check braking resistor value is greater than or equal to the minimum resistance value
Check braking resistor insulation
148
Electrical
Getting
Basic
installation
started
parameters
Source
xx
01
Drive size
1 to 4
5
06200XXX
06400XXX
06500XXX
xx
y
01
1
Running
NV Media Card
Optimization
the motor
Operation
y
zz
0
zz
Thermistor location in the drive defined by zz
Trip temperature (°C)
95
115
115
125
120
00: Rectifier snubber over current trip detected
Onboard
Advanced
Diagnostics
PLC
parameters
Description
Trip reset temperature (°C)
90
110
110
120