Figure 6-6 Unidrive SPMD and SPMC/U (rectifier) ground connections

Ground
link
The ground loop impedance must conform to the
requirements of local safety regulations.
The drive must be grounded by a connection capable of
carrying the prospective fault current until the protective
WARNING
device (fuse, etc.) disconnects the AC supply.
The ground connections must be inspected and tested at
appropriate intervals.
6.2

AC supply requirements

Voltage:
SPMX X2XX 200V to 240V ±10%
SPMX X4XX 380V to 480V ±10%
SPMX X6XX 500V to 690V ±10%
Number of phases: 3
Maximum supply imbalance: 2% negative phase sequence (equivalent
to 3% voltage imbalance between phases).
Frequency range: 48 to 62 Hz
The maximum supply symmetrical fault current must be limited to 100kA
(also required for UL compliance).
6.2.1
Supply types
Drives rated for supply voltage up to 575V are suitable for use with any
supply type, i.e. TN-S, TN-C-S, TT, IT, with grounding at any potential,
i.e. neutral, centre or corner ("grounded-delta").
Grounded delta supplies >575V are not permitted.
Unidrive SPM User Guide
Issue Number: 3
System
Mechanical
Electrical
Getting
Installation
Installation
Started
Supply
ground
Motor
ground
www.controltechniques.com
Basic
Running
SMARTCARD
Optimization
parameters
the motor
operation
Drives are suitable for use on supplies of installation category III and
lower, according to IEC60664-1. This means they may be connected
permanently to the supply at its origin in a building, but for outdoor
installation additional over-voltage suppression (transient voltage surge
suppression) must be provided to reduce category IV to category III.
Operation with IT (ungrounded) supplies:
Special attention is required when using internal or external
EMC filters with ungrounded supplies, because in the event
of a ground (earth) fault in the motor circuit the drive may not
WARNING
trip and the filter could be over-stressed. In this case, either
the filter must not be used (removed) or additional
independent motor ground fault protection must be provided.
Refer to Table 6-1.
For instructions on removal, refer to Figure 6-19 on page 80.
For details of ground fault protection contact the supplier of
the drive.
A ground fault in the supply has no effect in any case. If the motor must
continue to run with a ground fault in its own circuit then an input
isolating transformer must be provided and if an EMC filter is required it
must be located in the primary circuit.
Unusual hazards can occur on ungrounded supplies with more than one source,
for example on ships. Contact the supplier of the drive for more information.
Table 6-1 Behaviour of the drive in the event of a ground (earth)
fault with an IT supply
Drive
Internal filter only
size
May not trip – precautions
required:
SPMA
Remove the EMC filter
SPMD
Use ground leakage
relay
6.2.2
Input line reactor specifications
A separate input line reactor of at least the value shown in
Table 6-2 and Table 6-3 must be used with the rectifiers.
Failure to provide sufficient reactance could damage or
reduce the service life of the rectifier or inverter.
CAUTION

Figure 6-7 Input line reactor/output sharing choke dimensions

Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
External filter (with
internal)
May not trip – precautions
required:
Do not use EMC filter