Honeywell SLG 700 User Manual page 77

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Name (DTM/DD)
Display View6 corrupt
Display View7 corrupt
Display View8 corrupt
Device Variable Not
Supported
Volume Calculation
Failure
Linearization Table
Error
Revision 5
Description (Cause)
Display View6 database block found
corrupt.
Display View7 database block found
corrupt.
Display View8 database block found
corrupt.
This condition indicates that one of
the Dynamic Variables is mapped to
a Device Variable that is not
supported by the current Measured
Product. This condition is considered
non-critical for the SV, TV and QV
Dynamic Variables. However, if this
condition is true for the PV Dynamic
Variable, then the critical
Measurement Failure condition will
also be set.
This condition indicates that one of
the Dynamic Variables is mapped to
a Device Variable that calculates a
volume and the volume calculation
failed. This condition is considered
non-critical for the SV, TV and QV
Dynamic Variables. However, if this
condition is true for the PV Dynamic
Variable, then the critical
Measurement Failure condition will
also be set.
This condition indicates that one of
the Dynamic Variables is mapped to
a Device Variable that is derived from
a linearized level measurement and
the corrected level calculation failed.
This condition is considered non-
critical for the SV, TV and QV
Dynamic Variables. However, if this
condition is true for the PV Dynamic
Variable, then the critical
Measurement Failure condition will
also be set.
SLG 700 Series HART Option User's Manual
Resolution (Steps to take)
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view6 NVM data.
Power cycle the device. User will need
to reconfigure Display view6.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view7 NVM data.
Power cycle the device. User will need
to reconfigure Display view7.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view8 NVM data.
Power cycle the device. User will need
to reconfigure Display view8.
Reconfigure the dynamic variables PV,
SV, TV and QV correctly for the
configured measured product type. See
page 19.
Verify the strapping table data or the
dimensions of ideal tank shape.
Ensure that the Level linearization table
has at least two entries, that the entries
in both measured and corrected level
columns are in Ascending or
descending order and also all of the
entries are within the range specified by
the measurement configuration
parameters.
Page 69