Honeywell SLG 700 User Manual page 69

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Name (DTM/DD)
Device Configuration
Failure
Algorithm
Configuration DB
Corrupt
Common DB Corrupt
Revision 5
Description (Cause)
This is a roll-up status bit that is set
when any of the following critical status
conditions are present.
Algorithm Configuration DB
Corrupt
Common DB Corrupt
Sensor and Comm. Board DB
Data Mismatch
Sensor and Comm. Board DB
Version Mismatch
Sensor Characterization Data
Failure
Sensor Configuration DB Corrupt
Sensor Characterization Data
Failure
Sensor Parameter Write Failure
Vital Configuration DB Corrupt
Miscellaneous DB Corrupt
General Configuration DB Corrupt
Model Number Mismatch
The following non-critical conditions can
also cause this to be set.
Level linearization table 1 or table 2
corrupted in Communication Board
when linearization is Enabled
Volume Strapping table 1 or table 2
corrupted in Communication Board
when volume calculation type is
Strapping Table
NVM copy of Sensor algorithm
database block found corrupt.
NVM copy of Common database block
found corrupt.
SLG 700 Series HART Option User's Manual
Resolution (Steps to take)
Refer to each condition later in this
table.
Refer to Table 16 - HART Non-Critical
Diagnostic Messages page 65.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the algorithm
block NVM data.
Power cycle the device. If the problem
still persists then NVM might be
damaged so need to replace
Communication board. User may
require to configure the correlation
algorithm parameters if device does
not make valid level measurements.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the common
database block NVM data.
Power cycle the device.
If the problem still persists then NVM
might be damaged so need to replace
Communication module.
Page 61