Honeywell SLG 700 User Manual page 76

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Name (DTM/DD)
Meter (Display)
Timeout
Display NVM Corrupt
Display View1 corrupt
Display View2 corrupt
Display View3 corrupt
Display View4 corrupt
Display View5 corrupt
Page 68
Description (Cause)
Display module not connected
properly to Comm module or the
interface connector or hardware of
either Comm module or display
module is damaged.
Display configuration data has been
corrupted.
Display View1 database block found
corrupt.
Display View2 database block found
corrupt.
Display View3 database block found
corrupt.
Display View4 database block found
corrupt.
Display View5 database block found
corrupt.
SLG 700 Series HART Option User's Manual
Resolution (Steps to take)
Power cycle the device and check the
local display connectivity. Secure
Display connections and recheck
Refer to Maintenance in User manual
34-SL-25-11 for more details about how
to connect the display module with
Communication module.
If problem still persists, replace the
display module
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
general configurtaion NVM data.
Power cycle the device. Reconfigure
Display general configuration like
screen rotation, language and
password. If individual views are
corrupted then reconfigure the
corresponding view that is defaulted.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view1 NVM data.
Power cycle the device. User will need
to reconfigure Display view1.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view2 NVM data.
Power cycle the device. User will need
to reconfigure Display view2.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view3 NVM data.
Power cycle the device. User will need
to reconfigure Display view3.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view4 NVM data.
Power cycle the device. User will need
to reconfigure Display view4.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view5 NVM data.
Power cycle the device. User will need
to reconfigure Display view5.