Honeywell SLG 700 User Manual page 31

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Centering Disk Diameter
Probe Propagation Factor
Probe Length
Probe Details Image
Config. Blocking Dist
Block. Dist. High
(Read only)
Block. Dist. Low
(Read only)
Loop Current in BD
Revision 5
2 inches
3 inches
4 inches
6 inches
8 inches
0.9 to 1.1
Refer to SLG 700 Transmitter User's manual #34-SL-25-11
See B in image
See C in image
High Saturation,
Low Saturation,
Last Known Good value,
Default
SLG 700 Series HART Option User's Manual
A region near the flange where
measurements are not possible or are
inaccurate.
A region near the probe end where
measurements are not possible or are
inaccurate. This is somewhat dependent on
the DC of the material being measured.
Select behavior of the analog output when
the PV measurement is in the blocking
distance.
High Saturation: Sets loop current to either
20.5 or 20.8 based on Namur Selection.
Low Saturation: Sets loop current to 3.8
mA.
Last Known Good Value: Loop current
follows the last known PV value.
Default: If distance is in High zone, loop
current is set to high saturation current. If
distance is in Low zone set loop current to
3.8 mA.
Page 23