Honeywell SLG 700 User Manual page 28

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Key:
Plain = Read only
PV Levels Image
PV URV
PV LRV
PV Damp
PV % rnge
PV Loop current
PV Alrm typ
Loop current mode
Poll addr
Num req preams
Echo Lost Timeout
Page 20
Table 4 - Basic Configuration parameters, cont'd
Bold = Configurable
Bold underline = Method
4-20mA Outputs
#
#
#
#
#
#
#
SLG 700 Series HART Option User's Manual
Bold italic = Table or graph
.
Enter the measured PV upper range value
for which the analog output will be scaled
to 20 mA.
Enter the measured PV lower range value
for which the analog output will be scaled
to 4 mA.
Enter number of seconds damping time
applied to the analog output.
PV's value expressed as % of range.
PV's loop current (4-20mA).
Defines the loop current value when
device detects critical fault.
Hi: Loop current is set to more than 21mA
Low: Loop current is set to less than
3.6mA.
Enable: Enables loop current mode
(analog output will operate as a 4 to 20
mA signal consistent with the transmitter
output).
Disable: Disables loop current mode
(analog output will be fixed to value set by
user).
Address used by the Host to identify a
Field Device, and changeable by the User
to control: the Multidrop Mode for Analog
Output 1), and the Analog Output Fixed
Mode of Analog Output 1).
Number of request preambles required
from the Host request by the Field Device
for Synchronization.
Enter number of seconds. In case of Echo
is lost (peaks are not detected), device
waits for configured timeout to report fault.
Revision 5