Name (DTM/DD)
Common DB RAM
Corrupt
Miscellaneous DB
RAM Corrupt
Linearization Table 1
Config DB RAM corrupt
Linearization Table 2
Config DB RAM corrupt
Volume Strapping
Table 1 Config DB
RAM corrupt
Volume Strapping
Table 2 Config DB
RAM corrupt
Sensor Algorithm
Config DB RAM
Corrupt
Revision 5
Description (Cause)
RAM copy of Common database
block found corrupt.
RAM copy of Miscellaneous database
block found corrupt.
Level linearization table 1 RAM copy
of database block found corrupt.
This non critical alarm can occur even
linearization is disabled
Level linearization table 2 RAM copy
of database block found corrupt.
This non critical alarm can occur even
linearization is disabled
RAM copy of Volume strapping table
1 database block found corrupt.
This non critical alarm can occur even
volume calculation type is none
RAM copy of Volume strapping table
2 database block found corrupt.
This non critical alarm can occur even
volume calculation type is none
Sensor algorithm RAM copy of
database block found corrupt.
SLG 700 Series HART Option User's Manual
Resolution (Steps to take)
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device
If the problem persists even after power
cycle then Communication module
needs to be changed.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Page 73