Table 5 - Advanced Configuration parameters, cont'd
Key:
Plain = Read only
Bold = Configurable
Linearization
Disabled
Enabled
Config.
2-32
Linearization
Points In Use
Level Points
2-32
In Use
Linearization Table
Refresh
Linearization
Table
Length Unit
m
cm
(Read only)
mm
in
ft
Wet Linearization
Save Linear.
Date
Linearization
Records
Page 24
Bold underline = Method
Linearization
The linearization table in the transmitter is either Enabled or Disabled. When
enabled the transmitter's measured values are replaced by corresponding
user-specified corrected values from the linearization table.
Before enabling the user must first configure linearization table, then Send it to
the transmitter. Table can be updated either as complete block (dry calibration)
or single entry (wet calibration) measurements are active.
Note: The Level Linearization feature does not affect the values reported for
the Distance to Product and Distance to Interface device variables. If Level
Linearization is enabled, measured level are no longer described solely by the
basic geometry and it is possible that the Product Level will not be equal to
(Sensor Height – Level Offset – Distance to Product). Likewise for the
measured interface if is applicable based on measured product type.
Enter number of index points to be used in the dry and wet linearization tables.
The user can enter up to a maximum of 32 points to construct the tables.
In this table for dry linearization, the user can enter pairs of Measured Level
and a corresponding Corrected Level.
Press Send to download the table to the transmitter's memory. Table will be
used after Linearization is enabled.
Updates the table with recent changes made.
Length unit used in the linearization tables.
In this wet Linearization method, enter a linearized level for the corresponding
level. Press Send to download the table to the transmitter's memory.
Enter the date of creation for the linearization table.
Date of saved linearization table.
SLG 700 Series HART Option User's Manual
Bold italic = Table or graph
Revision 5