5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
FAULT REPORT 1
5
The F60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
Fault report number
Name of the relay, programmed by the user
Firmware revision of the relay
Date and time of trigger
Name of trigger (specific operand)
Line/Feeder ID via the name of a configured signal source
Active setting group at the time of trigger
Pre-fault current and voltage phasors (one-quarter cycle before the trigger)
Fault current and voltage phasors (three-quarter cycle after the trigger)
Elements operated at the time of triggering
Events: 9 before trigger and 7 after trigger (only available via the relay webpage)
Fault duration times for each breaker (created by the Breaker Arcing Current feature)
The fault locator does not report fault type or location if the source VTs are connected in the Delta configuration.
NOTE
The captured data also includes the fault type and the distance to the fault location, as well as the reclose shot number
(when applicable) The Fault Locator does not report fault type or location if the source VTs are connected in the Delta con-
figuration. To include fault duration times in the fault report, the user must enable and configure Breaker Arcing Current fea-
ture for each of the breakers. Fault duration is reported on a per-phase basis.
5-24

FAULT REPORTS

FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
MESSAGE
Off
FAULT REPORT 1 Z1
MESSAGE
MAG: 3.00 Ω
FAULT REPORT 1 Z1
MESSAGE
ANGLE: 75°
FAULT REPORT 1 Z0
MESSAGE
MAG: 9.00 Ω
FAULT REPORT 1 Z0
MESSAGE
ANGLE: 75°
FAULT REPORT 1 LINE
MESSAGE
LENGTH UNITS: km
FAULT REP 1 LENGTH
MESSAGE
(km
): 100.0
F60 Feeder Management Relay
FAULT REPORT 1
Range: SRC 1, SRC 2
Range: FlexLogic™ operand
Range: 0.01 to 250.00
Range: 25 to 90° in steps of 1
Range: 0.01 to 650.00
Range: 25 to 90° in steps of 1
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
5 SETTINGS
5.2.7 FAULT REPORTS
Ω
in steps of 0.01
Ω
in steps of 0.01
GE Multilin