5.2 PRODUCT SETUP
SERVER
CONFIGURATION
IEC 61850 LOGICAL
NODE NAME PREFIXES
5
MMXU DEADBANDS
GGIO2 CONTROL
CONFIGURATION
The F60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The F60 operates as an IEC 61850
server. The Remote Inputs/Outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The
REMOTE I/O TRANSFER METHOD
61850 GSSE, IEC 61850 GOOSE, or none (remote inputs/outputs disabled). GOOSE messages are more efficient and can
make use of Ethernet priority tagging and virtual LAN functionality. All relays exchanging remote input/output data must be
set to the same transfer method.
5-18
LD NAME: IECDevice
IEC/MMS TCP PORT
MESSAGE
NUMBER:
INCLUDE NON-IEC
MESSAGE
DATA: Enabled
NUMBER OF STATUS
MESSAGE
POINTS IN GGIO1:
SERVER SCANNING:
MESSAGE
Disabled
CLEAR XCBR1 OpCnt:
MESSAGE
No
CLEAR XCBR2 OpCnt:
MESSAGE
No
PIOC LOGICAL NODE
NAME PREFIXES
PTOC LOGICAL NODE
MESSAGE
NAME PREFIXES
PTRC LOGICAL NODE
MESSAGE
NAME PREFIXES
MMXU1 DEADBANDS
MMXU2 DEADBANDS
MESSAGE
MMXU3 DEADBANDS
MESSAGE
MMXU4 DEADBANDS
MESSAGE
GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 2
MESSAGE
GGIO2 CF SPCSO32
MESSAGE
selects the method used to transfer remote input/output data. This can be either IEC
F60 Feeder Management Relay
Range: up to 32 alphanumeric characters
Range: 1 to 65535 in steps of 1
102
Range: Disabled, Enabled
Range: 8 to 128 in steps of 8
8
Range: Disabled, Enabled
Range: No, Yes
Range: No, Yes