Interface - GE F60 Instruction Manual

Ur series
Hide thumbs Also See for F60:
Table of Contents

Advertisement

3 HARDWARE
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps only. The
setting is not applicable to this module.
RATE
NOTE
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to Pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if
Pin X1a or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrange-
ment of these pins, see the Rear Terminal Assignments section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3–33: TYPICAL PIN INTERCONNECTION BETWEEN TWO G.703 INTERFACES
Pin nomenclature may differ from one manufacturer to another. Therefore, it is not uncommon to see
pinouts numbered TxA, TxB, RxA and RxB. In such cases, it can be assumed that "A" is equivalent to "+"
NOTE
and "B" is equivalent to "–".
b) G.703 SELECTION SWITCH PROCEDURES
1.
Remove the G.703 module (7R or 7S):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2.
Remove the module cover screw.
3.
Remove the top cover by sliding it towards the rear and then lift it upwards.
4.
Set the Timing Selection Switches (Channel 1, Channel 2) to the desired timing modes.
5.
Replace the top cover and the cover screw.
GE Multilin
SETTINGS
G.703
CHANNEL 1
SURGE
G.703
CHANNEL 2
SURGE
Figure 3–32: G.703 INTERFACE CONFIGURATION
X
1a
Shld.
X
1b
Tx -
G.703
X
2a
Rx -
CHANNEL 1
X
2b
Tx +
X
3a
Rx +
X
3b
SURGE
X
6a
Shld.
X
6b
Tx -
G.703
X
7a
Rx -
CHANNEL 2
X
7b
Tx +
X
8a
Rx +
X
8b
SURGE
F60 Feeder Management Relay
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
PRODUCT SETUP
DIRECT I/O
X
1a
Shld.
X
1b
Tx –
X
2a
Rx –
2b
Tx +
X
X
3a
Rx +
X
3b
X
6a
Shld.
Tx –
X
6b
X
7a
Rx –
X
7b
Tx +
X
8a
Rx +
8b
X
831727A2-X1.CDR
X
1a
Shld.
X
1b
Tx -
G.703
X
2a
Rx -
CHANNEL 1
X
2b
Tx +
X
3a
Rx +
X
3b
SURGE
X
6a
Shld.
X
6b
Tx -
G.703
X
7a
Rx -
CHANNEL 2
X
7b
Tx +
X
8a
Rx +
8b
X
SURGE
831727A2.CDR
3.3.4 G.703 INTERFACE
DIRECT I/O DATA
3
3-27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents