B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 46)
ADDR
REGISTER NAME
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
4481
Phase CT 1 Secondary
4482
Ground CT 1 Primary
4483
Ground CT 1 Secondary
B
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
4501
Phase VT 1 Secondary
4502
Phase VT 1 Ratio
4504
Auxiliary VT 1 Connection
4505
Auxiliary VT 1 Secondary
4506
Auxiliary VT 1 Ratio
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
4583
Source 1 Phase CT
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking Function
Breaker Control (Read/Write Setting) (2 modules)
4700
Breaker 1 Function
4701
Breaker 1 Name
4704
Breaker 1 Mode
4705
Breaker 1 Open
4706
Breaker 1 Close
4707
Breaker 1 Phase A 3 Pole
4708
Breaker 1 Phase B
4709
Breaker 1 Phase C
470A
Breaker 1 External Alarm
470B
Breaker 1 Alarm Delay
470D
Breaker 1 Push Button Control
470E
Breaker 1 Manual Close Recall Time
4710
Breaker 1 Out Of Service
4711
Breaker 1 IEC 61850 XCBR.ST.Loc Status operand
4712
Reserved (6 items)
4718
...Repeated for Breaker 2
Synchrocheck (Read/Write Setting) (2 modules)
4780
Synchrocheck 1 Function
B-22
RANGE
1 to 65000
0 to 1
1 to 65000
0 to 1
0 to 1
50 to 240
1 to 24000
0 to 6
50 to 240
1 to 24000
---
0 to 63
0 to 63
0 to 63
0 to 63
25 to 60
0 to 1
0 to 5
0 to 1
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1000000
0 to 1
0 to 1000000
0 to 65535
0 to 65535
0 to 65535
0 to 1
F60 Feeder Management Relay
APPENDIX B
UNITS
STEP
FORMAT
A
1
F001
---
1
F123
A
1
F001
---
1
F123
---
1
F100
V
0.1
F001
:1
1
F060
---
1
F166
V
0.1
F001
:1
1
F060
---
---
F206
---
1
F400
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
---
1
F106
---
1
F167
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
s
1
F001
---
1
F102
DEFAULT
1
0 (1 A)
1
0 (1 A)
0 (Wye)
664
1
1 (Vag)
664
1
"SRC 1"
0
0
0
0
60
0 (ABC)
0 (SRC 1)
1 (Enabled)
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0 (Disabled)
GE Multilin