Siemens Simatic S7-1500 Manual page 59

Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Category
Parameter
Phase B
for "PTO (A, B
phase-shifted)" and
"PTO (A, B phase-
shifted, quadruple)"
Drive enable output
Reaction of the PTO channel to CPU STOP
The PTO channel reacts to a change to CPU STOP with the removal of the drive enable (to
the extent that the drive enable output is configured) and with output of the velocity setpoint
0 at the hardware outputs configured for the signal tracks A and B. The CPU STOP reaction
of the PTO channels cannot be configured.
Note
Reaction to CPU STOP
Upon CPU STOP, the hardware outputs assigned for the PTO outputs A and B can switch to
signal state 'High' (1) and/or remain there. A switching/remaining of the two hardware
outputs to/in signal level 'Low' (0) is not guaranteed.
Controller
The pulse output channels for the four modes of the pulse generators (PTO) are controlled
using Motion Control via the technology objects TO_SpeedAxis, TO_PositioningAxis and
TO_SynchronousAxis. With these operating modes, the control and feedback interface of the
channels is a partial implementation of the PROFIdrive interface "Telegram 3". For a detailed
description of the use of motion control and its configuration, refer to the S7-1500 Motion
Control function manual (http://support.automation.siemens.com/WW/view/en/59381279)
and the STEP 7 online help.
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Meaning
The "Clock generator output
(B)" parameter defines the
hardware output for PTO
signal B.
The parameter "Drive enable
output" defines the hardware
output of the output "Drive
enable output".
Value range
[Output address 1 of the DQ for
PTO signal B (output frequency
100 kHz)]
[Output addresses of the enable
output DQn (output frequency
100 Hz)
Technology functions
3.2 Pulse generators
Default
grayed out
Read only
access to the
parameter
--
59