Technical specifications
Cable length
shielded, max.
Analog value generation for the inputs
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including sign),
max.
Integration time configurable
Interference voltage suppression for interference
frequency f1 in Hz
Measured value smoothing
Configurable
Setting: None
Setting: Weak
Setting: Medium
Setting: Strong
Analog value generation for the outputs
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including sign),
max.
Settling time
For resistive load
For capacitive load
For inductive load
Encoders
Connection of the signal transmitters
For voltage measurement
For current measurement as 4-wire transducer
For resistance measurement with two-wire con-
nection
For resistance measurement with three-wire con-
nection
For resistance measurement with four-wire con-
nection
Connectable encoders
2-wire sensor
136
Permissible quiescent current (2-wire sensor),
max.
6ES7512-1CK00-0AB0
200 m
16 bits
Yes; 2.5 / 16.67 / 20 / 100 ms, acts on all chan-
nels
400 / 60 / 50 / 10
Yes
Yes
Yes
Yes
Yes
16 bits
1.5 ms
2.5 ms
2.5 ms
Yes
Yes
Yes
Yes
Yes
Yes
1.5 mA