Technical specifications
Interference voltage suppression for f = n x (f1 +/-
1%), f1 = interference frequency
Series-mode interference (peak of the interference
< rated value of the input range), min.
Common mode voltage, max.
Common mode interference, min.
Interfaces
Number of PROFINET interfaces
1st interface
Interface hardware
Number of ports
Integrated switch
RJ45 (Ethernet)
Protocols
PROFINET IO controller
PROFINET IO device
SIMATIC communication
Open IE communication
Web server
Media redundancy
PROFINET IO controller
Services
138
PG/OP communication
S7 routing
Isochronous mode
Open IE communication
IRT
MRP
MRPD
Prioritized startup
Number of connectable IO devices, max.
of these, IO devices with IRT, max.
Number of connectable IO devices for RT,
max.
of these in a line, max.
Number of IO devices that can be ena-
bled/disabled simultaneously, max.
Number of IO devices per tool, max.
Update times
6ES7512-1CK00-0AB0
30 dB
10 V
60 dB; at 400 Hz: 50 dB
1
2
Yes
Yes; X1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes; as MRP redundancy manager and/or MRP
client; max. number of devices in the ring: 50
Yes; requirement: IRT
Yes; max. 32 PROFINET devices
128; a total of up to 512 distributed I/O devices
can be connected via AS-i, PROFIBUS or
PROFINET
64
128
128
8; in total over all interfaces
8
Minimum value of update time also depends on
the communication allocation setting for
PROFINET IO, the number of IO devices and the
amount of configured user data.
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)