Control interface per channel
The following table shows the control interface assignment:
Table 3- 3
Assignment of the control interface
Offset from start
Parameter
address
Bytes 0 to 3
Slot 0
Bytes 4 to 7
Slot 1
Byte 8
LD_SLOT_0*
LD_SLOT_1*
Byte 9
EN_CAPTURE
EN_SYNC_DN
EN_SYNC_UP
SET_DQ1
SET_DQ0
TM_CTRL_DQ1
TM_CTRL_DQ0
SW_GATE
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Meaning
Load value (meaning of the value is specified in LD_SLOT_0)
Load value (meaning of the value is specified in LD_SLOT_1)
Specifies the meaning of the value in Slot 0
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
to
1
1
1
1
Specifies the meaning of the value in Slot 1
Bit 7
Bit 6
Bit 5
Bit 4
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
to
1
1
1
1
Bit 7: Enable capture function
Bit 6: Enable downward synchronization
Bit 5: Enable upward synchronization
Bit 4: Set DQ1
Bit 3: Set DQ0
Bit 2: Enable technological function DQ1
Bit 1: Enable technological function DQ0
Bit 0: Software gate
Technology functions
3.1 High-speed counters
No action, idle state
Load counter
Reserve
Load start value
Load comparison value 0
Load comparison value 1
Load low counting limit
Load high counting limit
Reserve
No action, idle state
Load counter
Reserve
Load start value
Load comparison value 0
Load comparison value 1
Load low counting limit
Load high counting limit
Reserve
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents