Parameters of PTO mode
Category
Parameter
Diagnostics
No supply voltage L+
interrupt
Data ex-
Reference speed
change with
the drive
Maximum speed
Increments per revo-
lution
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Meaning
With the parameter "No sup-
ply voltage L+" you activate
the diagnostic interrupt of the
channel in the case of no
supply voltage L+.
With the parameter "Refer-
ence speed" you define the
reference value for the drive
velocity. The drive velocity is
defined as percentage value
of the reference speed in the
range from -200 % to
+200 %.
The parameter "Maximum
speed" is used to define the
required maximum speed for
your application.
The "Increments per revolu-
tion" is used to define the
number of increments per
revolution (also in microstep
mode), which is required by
the drive for a revolution.
Value range
Deactivated
Activated
Floating-point number:
1.0 bis 20,000.0 (rpm)
The supported value range depends
on:
the signal type selected under
"Operating mode"
the value defined under "Incre-
ments per revolution"
the value defined under "Refer-
ence speed"
The low limit of the value range is:
for the signal type "PTO (A, B
phase-shifted - quadruple)":
0.1 Hz * 60 s/min * 4) / Incre-
ments per revolution
for the non-quadruple PTO sig-
nal types: (0.1 Hz * 60 s/min) /
increments per revolution
The high limit of the value range is
the minimum of the value:
2 * reference speed
and of the value:
for the signal type "PTO (A, B
phase-shifted - quadruple)":
(100 000 Hz * 60 s/min * 4) / In-
crements per revolution
for the non-quadruple PTO sig-
nal types:
(100 000 Hz * 60 s/min) / Increm
ents per revolution
1 to 1,000,000
Technology functions
3.2 Pulse generators
Default
Deactivated
3,000.0 (rpm)
3,000.0 (rpm)
200
57