Encoder signals, incremental encoder (asymme-
tric)
Input voltage
Input frequency, max.
Counting frequency, max.
Configurable signal filter
Incremental encoder with A/B tracks, 90° phased-
shifted
Incremental encoder with A/B tracks, 90° phased-
shifted and zero track
Pulse encoder
Pulse encoder with direction
Pulse encoder with one pulse signal per count
direction
Errors/accuracies
Linearity error (relative to input range), (+/-)
Temperature error (relative to input range), (+/-)
Crosstalk between the inputs, max.
Reproducibility in steady state condition at 25 °C
(relative to input range), (+/-)
Output ripple (relative to output range, bandwidth
0 to 50 kHz), (+/-)
Linearity error (relative to output range), (+/-)
Temperature error (relative to output range), (+/-)
Crosstalk between outputs, max.
Reproducibility in steady state condition at 25 °C
(relative to output range), (+/-)
Operational limit across the entire temperature
range
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Resistance, relative to input range, (+/-)
Resistance-type thermometer, relative to input
range, (+/-)
Voltage, relative to output range, (+/-)
Current, relative to output range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Resistance, relative to input range, (+/-)
Resistance-type thermometer, relative to input
range, (+/-)
Voltage, relative to output range, (+/-)
Current, relative to output range, (+/-)
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Technical specifications
6ES7512-1CK00-0AB0
24 V
100 kHz
400 kHz; with quadruple evaluation
Yes
Yes
Yes
Yes
Yes
Yes
0.1%
0.005%/K
-60 dB
0.05%
0.02%
0.15%
0.005%/K
-80 dB
0.05%
0.3%
0.3%
0.3%
Pt100 Standard: ±2 K, Pt100 Climatic: ±1 K,
Ni100 Standard: ±1.2 K, Ni100 Climatic: ±1 K
0.3%
0.3%
0.2%
0.2%
0.2%
Pt100 Standard: ±1 K, Pt100 Climatic: ±0.5 K,
Ni100 Standard: ±0.6 K, Ni100 Climatic: ±0.5 K
0.2%
0.2%