The following table shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing and the set interference frequency
suppression.
Table C- 2
Smoothing time depending on the set smoothing level and interference frequency suppression
Selection of the smoothing
(mean value generation from scan values)
None
Weak
Medium
Strong
Cycle time
The cycle times (1 ms, 1.04 ms and 1.25 ms) result from the configured interference
frequency suppression. The cycle time is independent of the number of configured analog
channels. The values for the analog input channels are detected sequentially in each cycle.
Reference
For more information on conversion time, cycle time and conversion method, refer to the
Analog value processing (http://support.automation.siemens.com/WW/view/en/67989094)
function manual.
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Interference frequency suppression/smoothing time
400 Hz
60 Hz
2.5 ms
16.6 ms
10 ms
66.4 ms
40 ms
265.6 ms
80 ms
531.2 ms
Analog value processing
C.1 Conversion method
50 Hz
10 Hz
20 ms
100 ms
80 ms
400 ms
320 ms
1600 ms
640 ms
3200 ms