Digital output functions, configurable
Switch at comparison values
PWM output
Frequency output
Pulse train
Switching capacity of outputs
with resistive load, max.
with lamp load, max.
Load resistance range
Low limit
High limit
Output voltage
Type of output voltage
for signal "0", max.
for signal "1", min.
Output current
for signal "1" rated value
for signal "1" permissible range, min.
for signal "1" permissible range, max.
for signal "0" residual current, max.
Output delay with resistive load
"0" to "1", max.
"1" to "0", max.
for technological functions
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Number, max.
Configurable cycle duration
On-load factor, min.
On-load factor, max.
Resolution of the on-load factor
"0" to "1", max.
"1" to "0", max.
Technical specifications
6ES7512-1CK00-0AB0
Yes; as output signal of a high-speed counter
Yes
4
Yes
0%
100%
0.0036 %; with S7 analog format, min. 40 ns
Yes
Yes; including for pulse/direction interface
0.5 A; 0.1 A at high-speed output, i.e. when a
high-speed output is used; refer to manual for
details
5 W; 1 W with high-speed output, i.e. when a
high-speed output is used; refer to manual for
details
48 W; 240 W with high-speed output, i.e. when a
high-speed output is used; refer to manual for
details
12 kΩ
DC
1 V; with high-speed output, i.e. when a high-
speed output is used; refer to manual for details
23.2 V; L+ (-0.8 V)
0.5 A; 0.1 A with high-speed output, i.e. when a
high-speed output is used; refer to manual for
details
2 mA
0.6 A; 0.12 A with high-speed output, i.e. when a
high-speed output is used; refer to manual for
details
0.5 mA
100 µs
500 μs; load-dependent
5 µs; dependent on output used, see additional
description in the manual
5 µs; dependent on output used, see additional
description in the manual