Using the Program
20
Item
Setback
Cooling Start
Temp.
Heating Start
Temp.
ERV
The following is the ERV control menu and features.
Item
Operation
GoTo
Room
Set Temperature
Mode
Fan Speed
[Detail.
] Button
(The setback function works well with "Heat Recovery" model. For other
models, it may not work properly.)
Set the setback function to control the proper room temperature when the
indoor unit is turned off.
[ON] Button: Enable temperature limits
[OFF] Button: Disable temperature limits
Click
/
to set the cooling start temperature
(21°C~40°C / 70°F~104°F).
Click
/
to set the heating start temperature (1°C~20°C / 34°F~68°F).
[ON] Button: Starts the operation of the device.
[Off] Button: Stops the operation of the device.
[Schedule ] Button: Move to Schedule menu.
Display the current temperature.
Click
/
to set a desired temperature (the ventilator is not activated).
[AUTO] Button: Evaluates the operating environment conditions and
automatically sets the optimum temperature.
[HEX] Button: Air supply and emissions are all ventilated through the heat
exchanger.
[NORM] Button: Ventilate emissions without passing through the heat
exchanger.
[LOW] Button: Slow fan speed.
[HIGH] Button: Fast fan speed.
[SUPER] Button: Maximum fan speed.
[AUTO] Button: Loops from LOW to HIGH to SUPER speeds.
Control details.
Description
Description