Functional Specifications ACP BACnet
160
Humidify Unit (Status)
Point number : 35
Object name : HumidifyUnitStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor the operating status of the humidifier.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Heater Unit (Status)
Point number : 36
Object name : HeaterUnitStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor the operating state of the heater.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Ventilation FAN (Status)
Point number : 37
Object name : VentilFANStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor the operating status of FAN ventilation.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Supply FAN (Status)
Point number : 38
Object name : VentilFANStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor the operating status of the air supply FAN.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status