Supply Humidity (Status)
Point number : 31
Object name : SupplyHumidifyStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the humidity of the air to be supplied.
Outdoor Humidity (Status)
Point number : 32
Object name : OutdoorHumidifyStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the humidity of the outside air.
Ventilation Humidity (Status)
Point number : 33
Object name : VentilHumidifyStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the humidity of the ventilation air is made.
CO
Value (Status)
2
Point number : 34
Object name : CO2ValueStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the humidity of the ventilation air is made.
Present Value property : 0~255
(Real Value = Value*10, Example : In case Value is 20, CO2 is 20*10=200ppm)
Functional Specifications ACP BACnet