Detailed Explanation of Object
Common to All Objects
Objects related to the air conditioner in communication are treated on the ACP BACnet as described below.
Air Conditioner in Normal Communication
- Other ACP BACnet devices can access each object related to the air conditioner.
Air Conditioner Unconnected
- It seems to other ACP BACnet devices that no objects related to the air conditioner exist.
- Therefore, when the ReadProperty/WriteProperty service is received, the following Er-
rorPDU will be returned.
- Error class: OBJECT; Error type: UNKNOWN_PROPERTY
Air Conditioner Communication Error
- Other BACnet device can access the objects related to the air conditioners, but the Present_
Value Property will be read in a value immediately before the communication error.
Run/Stop (Setting)
Point number: 1
Object name: StartStopCommand_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Output
Meaning: This object is used to give Run/Stop commands to the air conditioner.
Present_Value property:
ACTIVE: Run command
INACTIVE: Stop command
Remarks:
1. The command executed is transmitted to the A/C regardless of the status of the A/C.
2. Present_Value property will not be used if a property has never been set in the past.
Run/Stop (Status)
Point number: 2
Object name: StartStopStatus_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the Run/Stop status of the air conditioner.
Present_Value property:
ACTIVE: Run
INACTIVE: Stop
Remarks: If there is an operation error, the Present_Value property will be set to ACTIVE
regardless of whether the A/C is in operation or not.
Functional Specifications ACP BACnet
149