Current OA Damper (Status)
Object name : CurOADamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the current opening degree of OA damper.
Current EA Damper (Status)
Point number : 40
Object name : CurEADamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the current opening degree of the EA damper.
Current MIX Damper (Status)
Point number : 41
Object name : CurMixDamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the damper current Mix.
Cool OA Damper (Setting)
Point number : 42
Object name : OADamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of OA damper cooling.
Cool OA Damper (Status)
Point number : 43
Object name : OADamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of OA damper cooling that has
been set.
Functional Specifications ACP BACnet
161