Functional Specifications ACP BACnet
162
Cool EA Damper (Setting)
Point number : 44
Object name : EADamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of the EA damper cooling.
Cool EA Damper (Status)
Point number : 45
Object name : EADamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the EA damper cooling that
Cool MIX Damper (Setting)
Point number : 46
Object name : MIXDamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the degree of opening of the MIX cooling damper.
Cool MIX Damper (Status)
Point number : 47
Object name : MIXDamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the MIX cooling damper has
has been set.
been set.