Functional Specifications ACP BACnet
156
Set Temperature (Status)
Object name: SetTempStatus_XXX (XXX: AHU address)
Object type: Analog Input
Meaning: This object is used to monitor the set temperature of the A/C's control authority.
Present_Value property:
Temperature(°C)
Remarks : This object is for indoor units only, and reports the room temperature data
Fire Alarm (Setting)
Point number : 20
Object name : FireAlarmCommand_XXX (XXX : AHU address)
Object type : Binary Output
Meaning : This object is used to set the fire detection function.
Present Value property :
ACTIVE : Run command
INACTIVE : Stop command
Fire Alarm (Status)
Point number : 21
Object name : FireAlarmStatus_XXX (XXX:AHU address)
Object type : Binary Input
Meaning : This object is used to determine whether fire detection function settings.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Set Humidify (Setting)
Point number : 22
Object name : SetHumidifyCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set desired humidity function.
Present Value property : 40~60
measured by the indoor units.