LG PQNFB17C1 Installation And User Manual page 167

V-net acs
Table of Contents

Advertisement

Error Code
Point number: 16
Object name: MalfunctionCode_XXX (XXX: Indoor/Vent/AHU address)
Object type: Analog Input
Meaning: This object is used to monitor the details of the error status when the air conditioner
has an error.
Present_Value property:
Error code(Range is 1 to 255)
Remarks: This object's error code descriptions should be referred to the corresponding table
at the "Reference LG original Error Code".
User Mode (Setting)
Point number: 17
Object name: UserModeCommand_XXX (XXX: Vent address)
Object type: Multi-state Output
Meaning: This object is used to set the basic operation mode in vent and also additional
operation mode (quick fresh, energy efficiency, and heating).
Present_Value property:
1 : Quick
2 : Saving
3 : Heater
Remarks: This object is for vent only, and will not apply if the property has not been set in the
past.
User Mode (Status)
Point number: 18
Object name: UserModeStatus_XXX (XXX: Vent address)
Object type: Multi-state Input
Meaning : This object is used to monitor the basic operation mode in vent
Property_Value property:
1 : Quick
2 : Saving
3 : Heater
Reamark : This object is for vent only, and will not apply if the property has not been in the
past.
Functional Specifications ACP BACnet
155

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acp bacnetPqnfb17c0

Table of Contents